Final Checklist

Before Leaving the Installation Site, Verify:

All wiring has been done correctly in a workmanlike way, is secure and meets all applicable codes.

AquaSmart control temperature settings, differentials and optional functions are correctly set.

The control program is functioning properly by observing at least one complete cycle.

At shutdown, the temperature and pressure level match the recommended settings.

The pressure relief valve operation and boiler water feed system works properly by bleeding some water and observing the refill cycle.

The low water cutoff operation by lowering the water level until it shuts the burner off.

The boiler passages and vent system are clear of obstructions and operating to the appliance manufacturer’s specifications and all required clearance dimensions to combustible materials are met.

With combustion test instruments the burner is set to manufacturer’s specifications.

After the system has run through a complete cycle, that all fittings are free of leaks.

A record has been made of all service work and all temperature control settings and optional functions. Attach a label or tag to the boiler for future reference.

The AquaSmart Installation Manual is left at a suitable location near the boiler for future reference and the equipment owner is informed of this.

The control door is attached and securely closed.

Service

During Annual Maintenance or More Frequent Service Intervals, Verify the below items.

Note: The 7600 control has no serviceable internal parts. DO NOT attempt to repair a malfunctioning control.

The control is clean and all vents are free of dust, lint or foreign material.

All wiring is tight, terminals are free from corrosion and insulation is intact.

There is no physical damage to the case or display.

There is no evidence of water damage on the control or terminals.

The control is securely mounted to the well or other mounting support.

The sensor is in its place, with no evidence of tampering.

The sensor lead on remote mounted units is in good condition and securely anchored in the immersion well with the strain relief.

The control temperatures, differentials and optional functions are set correctly and working to established specifications. Consult the service tag or label on the boiler.

A record of service and any adjustments are made to the service label or tag.

The control door is attached and securely closed.

Accessories

AquaSmart Remote Mount Unit Pack • 7600RMU

Includes:

Cable Assembly with Coupler

Mounting Template

Self-drilling Screws (Qty:3)

Cable Ty-wrap

AquaSmart Temperature Sensor Unit Pack • 7600TSU

Includes:

Temperature Sensor

Cable Ty-wrap

Joint Compound

Installation Instructions

AquaSmart 2-in-1 Sensor Unit Pack • 76002N1S01U

Includes:

2-in-1 Sensor

36” Ground Wire

Pipe Clamp for grounding

Installation Instructions

AquaSmart Boiler Control Manual

33

Image 33
Contents Description / Applications Features Table of ContentsElectrical Shock Hazard Technical SpecificationsElectrical Ratings Environmental RatingsInstallation MountingSensor/Immersion Well Mounting Surface Mounting Burn, Scald, Explosion, and Equipment Malfunction Hazard AquaSmart Models and Cross-Reference GuideFrom previous Installing the Temperature Sensor Removing the Control to be Replaced Electrical shock hazardBurn and Scald Hazard 8 hex Explosion Burn and Scald HazardsThis is very important for successful control operation In-1 Installation InstructionsInstalling the AquaSmart Control WiringImmersion Well or 2-in-1 Sensor Appliance SurfaceSome Thermostats Are Polarity Sensitive Wiring the AquaSmart ControlWater Flow Control Wiring7600A/B multi-zone connections Control Wiring Option 2 Circulator-On Delay on All Zones Taco Honeywell Control Wiring Option 1 7600B onlyTaco Honeywell Control Wiring Option 2 7600A onlyDHW With Indirect Domestic Hot Water DHW Limit Zone Relay Circulator Control Wiring Option 3 Utilizing a Zone Panel On Next Honewell Taco Temperature Low Limit Temperature High LimitTemperature High Limit Differential Programming Basic FunctionsChanging the Heat Manager Settings Temperature Low Limit DifferentialProgramming Additional Options Viewing the Boiler Cycle HistoryKey for steps B3 & B5 Changing the Circulator SettingsChanging Domestic Hot Water Priority Dhwp Setting Selecting Fahrenheit or Celsius Temperature DisplayChanging Low Water Cut-Off Lwco Setting AquaSmart Boiler Control Manual Control Checkout Procedure AquaSmart OperationSystem Action AquaSmart Response How a Boiler Control Works Display Boiler Status Mode TroubleshootingHeatManager Technology LockoutFinal Checklist ServiceAccessories Page Mounting Template Limited Warranty Information