Final Checklist
Before Leaving the Installation Site, Verify:
□All wiring has been done correctly in a workmanlike way, is secure and meets all applicable codes.
□AquaSmart control temperature settings, differentials and optional functions are correctly set.
□The control program is functioning properly by observing at least one complete cycle.
□At shutdown, the temperature and pressure level match the recommended settings.
□The pressure relief valve operation and boiler water feed system works properly by bleeding some water and observing the refill cycle.
□The low water cutoff operation by lowering the water level until it shuts the burner off.
□The boiler passages and vent system are clear of obstructions and operating to the appliance manufacturer’s specifications and all required clearance dimensions to combustible materials are met.
□With combustion test instruments the burner is set to manufacturer’s specifications.
□After the system has run through a complete cycle, that all fittings are free of leaks.
□A record has been made of all service work and all temperature control settings and optional functions. Attach a label or tag to the boiler for future reference.
□The AquaSmart Installation Manual is left at a suitable location near the boiler for future reference and the equipment owner is informed of this.
□The control door is attached and securely closed.
Service
During Annual Maintenance or More Frequent Service Intervals, Verify the below items.
Note: The 7600 control has no serviceable internal parts. DO NOT attempt to repair a malfunctioning control.
□The control is clean and all vents are free of dust, lint or foreign material.
□All wiring is tight, terminals are free from corrosion and insulation is intact.
□There is no physical damage to the case or display.
□There is no evidence of water damage on the control or terminals.
□The control is securely mounted to the well or other mounting support.
□The sensor is in its place, with no evidence of tampering.
□The sensor lead on remote mounted units is in good condition and securely anchored in the immersion well with the strain relief.
□The control temperatures, differentials and optional functions are set correctly and working to established specifications. Consult the service tag or label on the boiler.
□A record of service and any adjustments are made to the service label or tag.
□The control door is attached and securely closed.
Accessories
AquaSmart Remote Mount Unit Pack • 7600RMU
Includes:
○Cable Assembly with Coupler
○Mounting Template
○
○Cable
AquaSmart Temperature Sensor Unit Pack • 7600TSU
Includes:
○Temperature Sensor
○Cable
○Joint Compound
○Installation Instructions
AquaSmart 2-in-1 Sensor Unit Pack • 76002N1S01U
Includes:
○
○36” Ground Wire
○Pipe Clamp for grounding
○Installation Instructions
AquaSmart Boiler Control Manual | 33 |