F174 |
| F177 | |
|
|
| |
Base Frequency 3 | Direct Access Number — | F174 | |
Program ⇒ Motor ⇒ Motor Set #3 | Parameter Type — Numerical | ||
The Base Frequency 3 setting is the frequency at which the output voltage of | Factory Default — 60.0 |
| |
Changeable During Run — Yes | |||
the ASD reaches its maximum setting. The Base Frequency Voltage 3 | |||
|
| ||
parameter is set at is set at F175. | Minimum — 25.0 |
| |
This parameter is used only when the parameters for motor set #3 are | Maximum — 299.0 |
| |
configured and selected. Motor set #3 may be selected by a properly configured | Units — Hz |
| |
input terminal (see Table 5 on pg. 236). |
| ||
|
| ||
For proper motor operation, the Base Frequency should be set for the name- |
|
| |
plated frequency of the motor. |
|
| |
|
|
| |
Base Frequency Voltage 3 | Direct Access Number — | F175 | |
Program ⇒ Motor ⇒ Motor Set #3 | Parameter Type — Numerical | ||
The Base Frequency Voltage 3 setting is the Motor #3 output voltage at the | Factory Default — | ||
Changeable During Run — Yes | |||
Base Frequency (F174). Regardless of the programmed value, the output | |||
|
| ||
voltage cannot be higher than the input voltage. | Minimum — 50.0 |
| |
The actual output voltage will be influenced by the input voltage of the ASD | Maximum — 660.0 |
| |
and the Supply Voltage Compensation setting (F307). | Units — Volts |
| |
|
|
This parameter is used only when the parameters for motor set #3 are configured and selected. Motor set #3 may be selected by a properly configured input terminal (see Table 5 on pg. 236).
Manual Torque Boost 3
Program ⇒ Motor ⇒ Motor Set #3
The Manual Torque Boost 3 function is used to increase the low frequency torque for high inertia loads by increasing the output voltage at frequencies below ½ of the Base Frequency 3 setting (F174).
See parameter F016 (Manual Torque Boost 1) for an explanation of torque boost.
This parameter is used only when the parameters for motor set #3 are configured and selected. Motor set #3 may be selected by a properly configured input terminal (see Table 5 on pg. 236).
Direct Access Number — F176
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Motor Overload Protection Level 3
Program ⇒ Motor ⇒ Motor Set #3
The Motor 3 Overload Protection Level parameter specifies the motor overload current level for motor set #3. This value is entered as either a percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps (A/V) or it may be set as a percentage of the ASD rating. The
The Motor 3 Overload Protection Level setting will be displayed in Amps if the EOI display units are set to A/V rather than %.
Direct Access Number — F177
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10
Maximum — 100
Units — %
H9 ASD Installation and Operation Manual | 99 |