F515

F521

Deceleration Time 4

Program Special Accel/Decel #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go from the Maximum Frequency to 0.0 Hz for the #4 Deceleration profile. The Accel/Decel pattern may be set using F502. The minimum Accel/Decel time may be set using F508.

Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads. Automatic Accel/Decel, Stall, and Ridethrough settings may lengthen the deceleration times.

Direct Access Number — F515

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Acceleration/Deceleration Pattern 4

Direct Access Number —

F516

Program Special Accel/Decel #1 – #4 Settings

Parameter Type — Selection List

This parameter enables a user-selected preprogrammed output profile that

Factory Default — Linear

 

Changeable During Run — Yes

controls the acceleration and deceleration pattern for the #4 Accel/Decel

 

 

parameter.

 

 

Settings:

 

 

0 — Linear

 

 

1 — S-Pattern 1

 

 

2 — S-Pattern 2

 

 

 

 

 

Acceleration/Deceleration Switching Frequency 3

Direct Access Number —

F517

Program Special Accel/Decel Special

Parameter Type — Numerical

This parameter sets the frequency at which the acceleration control is switched

Factory Default — 0.00

 

Changeable During Run — Yes

from the Accel #3 profile to the Accel #4 profile during a multiple-acceleration

 

 

profile configuration.

Minimum — 0.00

 

 

Maximum — Max. Freq. (F011)

 

Units — Hz

 

 

 

 

Pattern Operation Selection

Direct Access Number —

F520

Program Pattern Run Pattern Run

Parameter Type — Selection List

Pattern Run operation is enabled by selecting Seconds or Minutes as a unit of

Factory Default — Disabled

 

Changeable During Run — No

measure for the Operation Time setting for the selected Preset Speeds.

 

 

See Parameter F523 for more information on Selections and Group Speeds

 

 

setup.

 

 

Settings:

 

 

0 — Disabled

 

 

1 — Enabled (units in seconds)

 

 

2 — Enabled (units in minutes)

 

 

 

 

 

Pattern Operation Mode

Direct Access Number —

F521

Program Pattern Run Pattern Run

Parameter Type — Selection List

 

Factory Default — Reset After Stop

This parameter sets the start condition of subsequent Pattern Runs after the

initial Pattern Run has been terminated or has completed its programming.

Settings:

0 — Reset After Stop

1 — Continue After Stop

Changeable During Run — No

170

H9 ASD Installation and Operation Manual

Page 178
Image 178
Toshiba H9 operation manual F515 F521, Pattern Operation Selection, Pattern Operation Mode