F902

 

F905

 

 

 

Input Function Target 2

Direct Access Number —

F902

Program My Function My Function Unit 1

Parameter Type — Selection List

This parameter plays a role in the setup of the My Function feature by

Factory Default — 0 (Disabled)

Changeable During Run — Yes

selecting the functionality of the programmable Input Function Target 2

 

 

terminal.

 

 

This setting assigns the function of the programmable Input Function Target 2

 

 

terminal to any one of the user-selectable functions listed in Table 7 on pg. 240,

 

 

Table 8 on pg. 241, or Table 10 on pg. 243.

 

 

See F977 for more information on this parameter.

 

 

 

 

 

Input Function Command 2

Direct Access Number —

F903

Program My Function My Function Unit 1

Parameter Type — Selection List

This parameter is used to assign a user-selected logical operator to two user-

Factory Default — 0 (NOP)

 

 

 

selected Input Function Target variables, enable a counter/timer function, or

 

 

perform a hold/reset function.

 

 

Table 11 on pg. 245 lists the available selections. Their use and selection

 

 

requirements are described in an example at F977.

 

 

 

 

 

Input Function Target 3

Direct Access Number —

F904

Program My Function My Function Unit 1

Parameter Type — Selection List

This parameter plays a role in the setup of the My Function feature by

Factory Default — 0 (Disabled)

Changeable During Run — Yes

selecting the functionality of the programmable Input Function Target 3

 

 

terminal.

 

 

This setting assigns the function of the programmable Input Function Target 3

 

 

terminal to any one of the user-selectable functions listed in Table 7 on pg. 240,

 

 

Table 8 on pg. 241, or Table 10 on pg. 243.

 

 

See F977 for more information on this parameter.

 

 

 

 

 

Output Function Assigned

Direct Access Number —

F905

Program My Function My Function Unit 1

Parameter Type — Selection List

 

Factory Default — 0 (Disabled)

This parameter plays a role in the setup of the My Function feature by

selecting the functionality of the Output Function Assigned terminal.

Changeable During Run — Yes

This setting assigns the function of the programmable Output Function Assigned data location to one of the functions listed in the Input Setting field of Table 7 on pg. 240.

Settings:

0 – 3099

See the My Function Instruction Manual (P/N 58692) and F977 for more information on this parameter.

216

H9 ASD Installation and Operation Manual

Page 224
Image 224
Toshiba H9 operation manual F902 F905, Output Function Assigned