F743

 

F801

 

 

 

Trace Data 2

Direct Access Number —

F743

Program Utilities Trace

Parameter Type — Selection List

This parameter is used to select the Trace Data 2 item from Table 9 on pg. 242

Factory Default — Freq. Reference

Changeable During Run — Yes

to be read and stored in accordance with the setup of parameters F740 and

 

 

F741.

 

 

See F740 for more information on this parameter setting.

 

 

 

 

 

Trace Data 3

Direct Access Number —

F744

Program Utilities Trace

Parameter Type — Selection List

This parameter is used to select the Trace Data 3 item from Table 9 on pg. 242

Factory Default — Output Current

Changeable During Run — Yes

to be read and stored in accordance with the setup of parameters F740 and

 

 

F741.

 

 

See F740 for more information on this parameter setting.

 

 

 

 

 

Trace Data 4

Direct Access Number —

F745

Program Utilities Trace

Parameter Type — Selection List

This parameter is used to select the Trace Data 4 item from Table 9 on pg. 242

Factory Default — DC Voltage

Changeable During Run — Yes

to be read and stored in accordance with the setup of parameters F740 and

 

 

F741.

 

 

See F740 for more information on this parameter setting.

 

 

 

 

 

Baud Rate (RS485 2-wire)

Direct Access Number —

F800

Program Communications Communication Settings

Parameter Type — Selection List

This parameter plays a role in the setup of the communications network by

Factory Default — 19200

 

 

 

establishing the Baud Rate of the communications link.

Changeable During Run — Yes

The communications network includes other ASDs and Host/Control computers

Units — bps

 

that monitor the status of the ASD(s), transfers commands, and loads or

 

 

modifies the parameter settings of the ASD.

 

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

Settings:

 

 

0 — 9600

 

 

1 — 19200

 

 

2 — 38400

 

 

 

 

 

Parity (RS485 2- and 4-wire)

Direct Access Number —

F801

Program Communications Communication Settings

Parameter Type — Selection List

This parameter plays a role in the setup of the communications network by

Factory Default — Even Parity

 

 

establishing the Parity setting of the communications link.

Changeable During Run — Yes

The communications network includes other ASDs and Host/Control computers that monitor the status of the ASD(s), transfers commands, and loads or modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

0 — No Parity

1 — Even Parity

2 — Odd Parity

204

H9 ASD Installation and Operation Manual

Page 212
Image 212
Toshiba H9 operation manual F743 F801, Baud Rate RS485 2-wire, Parity RS485 2- and 4-wire