F743 |
| F801 | |
|
|
| |
Trace Data 2 | Direct Access Number — | F743 | |
Program ⇒ Utilities ⇒ Trace | Parameter Type — Selection List | ||
This parameter is used to select the Trace Data 2 item from Table 9 on pg. 242 | Factory Default — Freq. Reference | ||
Changeable During Run — Yes | |||
to be read and stored in accordance with the setup of parameters F740 and | |||
|
| ||
F741. |
|
| |
See F740 for more information on this parameter setting. |
|
| |
|
|
| |
Trace Data 3 | Direct Access Number — | F744 | |
Program ⇒ Utilities ⇒ Trace | Parameter Type — Selection List | ||
This parameter is used to select the Trace Data 3 item from Table 9 on pg. 242 | Factory Default — Output Current | ||
Changeable During Run — Yes | |||
to be read and stored in accordance with the setup of parameters F740 and | |||
|
| ||
F741. |
|
| |
See F740 for more information on this parameter setting. |
|
| |
|
|
| |
Trace Data 4 | Direct Access Number — | F745 | |
Program ⇒ Utilities ⇒ Trace | Parameter Type — Selection List | ||
This parameter is used to select the Trace Data 4 item from Table 9 on pg. 242 | Factory Default — DC Voltage | ||
Changeable During Run — Yes | |||
to be read and stored in accordance with the setup of parameters F740 and | |||
|
| ||
F741. |
|
| |
See F740 for more information on this parameter setting. |
|
| |
|
|
| |
Baud Rate (RS485 | Direct Access Number — | F800 | |
Program ⇒ Communications ⇒ Communication Settings | Parameter Type — Selection List | ||
This parameter plays a role in the setup of the communications network by | Factory Default — 19200 |
| |
|
| ||
establishing the Baud Rate of the communications link. | Changeable During Run — Yes | ||
The communications network includes other ASDs and Host/Control computers | Units — bps |
| |
that monitor the status of the ASD(s), transfers commands, and loads or |
|
| |
modifies the parameter settings of the ASD. |
|
| |
Changes made to this parameter require that the power be cycled (Off then On) |
|
| |
for the changes to take effect. |
|
| |
Settings: |
|
| |
0 — 9600 |
|
| |
1 — 19200 |
|
| |
2 — 38400 |
|
| |
|
|
| |
Parity (RS485 2- and | Direct Access Number — | F801 | |
Program ⇒ Communications ⇒ Communication Settings | Parameter Type — Selection List | ||
This parameter plays a role in the setup of the communications network by | Factory Default — Even Parity | ||
|
| ||
establishing the Parity setting of the communications link. | Changeable During Run — Yes |
The communications network includes other ASDs and Host/Control computers that monitor the status of the ASD(s), transfers commands, and loads or modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.
Settings:
0 — No Parity
1 — Even Parity
2 — Odd Parity
204 | H9 ASD Installation and Operation Manual |