Input Terminal 15 (LI7) Function
Program ⇒ Terminal ⇒ Input Terminals
This parameter is used to set the functionality of the LI7 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or Normally Closed.
This setting assigns the function of the programmable LI7 terminal to any one of the
Note: The Expansion IO Card Option 2 option board (P/N ETB004Z) is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for more information on the function of this terminal.
Direct Access Number — F125
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Input Terminal 16 (LI8) Function
Program ⇒ Terminal ⇒ Input Terminals
This parameter is used to set the functionality of the LI8 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or Normally Closed.
This setting assigns the function of the programmable LI8 terminal to any one of the
Note: The Expansion IO Card Option 2 option board (P/N ETB004Z) is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for more information on the function of this terminal.
Direct Access Number — F126
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
UT1
UT2
Output Terminal 1 (OUT1) Function | Direct Access Number — F130 | |
Program ⇒ Terminal ⇒ Output Terminals | Parameter Type — Selection List | |
This parameter is used to set the functionality of the OUT1 discrete output | Factory Default — Low Speed Signal | |
Changeable During Run — No | ||
terminals O1A and O1B. | ||
| ||
The O1A and O1B (OUT1) output terminals change states (open or close) as a |
| |
function of a |
| |
assignments for the OUT1 terminals. |
| |
In addition, the output terminals must be specified as Normally Open or |
| |
Normally Closed. |
| |
See parameter F669 for more information on this setting. |
| |
|
| |
Output Terminal 2 (OUT2) Function | Direct Access Number — F131 | |
Program ⇒ Terminal ⇒ Output Terminals | Parameter Type — Selection List | |
| Factory Default — RCH (Acc/Dec |
This parameter is used to set the functionality of the OUT2 discrete output terminals O2A and O2B.
The O2A and O2B (OUT2) output terminals change states (open or close) as a function of a
In addition, the output terminals must be specified as Normally Open or Normally Closed.
Complete)
Changeable During Run — No
See parameter F669 for more information on this setting.
92 | H9 ASD Installation and Operation Manual |