F633 | F637 | |
|
| |
V/I Analog Input Broken Wire Detection Level | Direct Access Number — F633 | |
Program ⇒ Terminal ⇒ Input Special Functions | Parameter Type — Numerical | |
This parameter is enabled by providing a | Factory Default — 0 (Disabled) | |
Changeable During Run — No | ||
monitors the V/I input signal and if the V/I input signal falls below the level | ||
| ||
specified here and remains there for a period of 0.3 seconds or more a trip will | Minimum — 1 | |
be incurred | Maximum — 100 | |
| ||
This value is entered as 0% to 100% of the V/I input signal range. | Units — % | |
|
| |
Annual Average Ambient Temperature | Direct Access Number — F634 | |
Program ⇒ Special ⇒ Special Parameters | Parameter Type — Selection List | |
This parameter is used in conjunction with a discrete output terminal setting to | Factory Default — Under 30° | |
Changeable During Run — No | ||
notify the operator of the remaining useful life of critical components of the | ||
| ||
ASD system. |
| |
With a discrete output terminal set to Part Replacement Alarm (see Table 8 on |
| |
pg. 241) and the calculation derived from the parameter setting, maintenance |
| |
scheduling may be enhanced. |
| |
Settings: |
| |
1 — Under 10° C (50° F) |
| |
2 — Under 20° C (68° F) |
| |
3 — Under 30° C (86° F) |
| |
4 — Under 40° C (104° F) |
| |
5 — Under 50° C (122° F) |
| |
6 — Under 60° C (140° F) |
| |
|
| |
Rush Relay Current Activation Time | Direct Access Number — F635 | |
Program ⇒ Special ⇒ Special Parameters⇒ Rush Relay Current | Parameter Type — Numerical | |
Activation Time | Factory Default — 0.0 | |
At system startup, this parameter sets a | Changeable During Run — No | |
| ||
Relay activation in an attempt to allow the DC bus voltage to reach the normal | Minimum — 0.0 | |
operating level before outputting a signal to the motor. | Maximum — 2.5 | |
| ||
| Units — Seconds |
PTC1 Thermal Selection
Program ⇒ Special ⇒ Special Parameters⇒ PTC1 Thermal Selection
This parameter Enables/Disables the optional external thermal detection circuit of the Expansion IO Card Option 1. A thermistor is connected from TH1+ to TH1- of TB3 on the Expansion IO Card Option 1.
Should the thermistor resistance reading fall below 50Ω because of an over- temperature condition or exceed 3000Ω because of an open circuit an External Thermal Fault (OH2) will be incurred.
Direct Access Number — F637
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Note: While this parameter is Enabled, the system cannot be restarted until the thermistor value recovers to the level of 1.8kΩ from an
Settings:
0 — Disabled
1 — Detect Disconnect
H9 ASD Installation and Operation Manual | 191 |