H9 ASD Installation and Operation Manual 229

Analog Function Assigned Object 21

Program My Function My Function Analog
This parameter plays a role in the setup of th e My Function feature by
selecting the function ality to which the adju stment of F962 is applied.
Settings:
0 — Disabled (None)
1 — Acceleration Rat e
2 — Upper Limit Frequency
3 — Acceleration Multi plication Factor
4 — Deceleration Multi plication Factor
5 — Manual Torque Boost
6 — Over Current Stal l (F601)
7 — Thermal Protection
8 — Speed Loop P Gain (F460)
9 — Drooping Gain (F320)
10 — PID P Gain (F362)
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and oper atio nal inform ati on of the Analog
Function Assigned Object parameter.
Direct Access Number — F964
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes

Monitor Output Function 11

Program My Function My Function Monitor
This parameter plays a role in the setup of th e My Function feature by
establishing the function that is to be recor d ed and output as the Peak,
Minimum, or Average value as selected at parameter F966.
Select the Monitor Display Input Setting number from Table 10 on pg. 243 to
output the corresponding function.
Use the Communication Number if operating usin g communications.
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the
Monitor Output Func tion parameter.
Direct Access Number — F965
Parameter Type — Selection List
Factory Default — 2000
Changeable During Run — Yes

Monitor Output Function Command 11

Program My Function My Function Monitor
This parameter plays a ro le in the setup of the My Function feature by allowing
the user to select the Peak, Minimum, or Normal (Avg.) value of the
parameter F965 selection to be recorded and output as a monitored functio n.
Settings:
0 — Normal
1 — Peak
2 — Minimum
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the
Monitor Output Func tion parameter.
Direct Access Number — F966
Parameter Type — Selection List
Factory Default — Normal
Changeable During Run — Yes
F964 F966