F826

F830

ASD-to-ASD Communications (RS485 4-wire)

Program Communications Communication Settings

The function of this parameter is 2-fold:

1)In a Master/Follower configuration and while communicating via RS485 4-wire, this parameter sets the ASD as the Master or the Follower.

2)This parameter determines the function of the ASD while operating as the

Master or the Follower. If operating as the Master ASD, an output parameter of the Master ASD is used to control the Follower ASDs and is set here. If operating as a Follower ASD, the ASD response if an error is incurred is set here.

Direct Access Number — F826 Parameter Type — Selection List Factory Default — Follower (Decel Stop) Changeable During Run — Yes

Note: Select a Follower function here if F806 is configured as a

Master Output controller for any other ASD in the system.

Otherwise, an EOI failure will result.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

0 — Follower (Decel Stop if error detected)

1 — Follower (Continues operation if error detected)

2 — Follower (Emergency Off if error detected)

3 — Master (Frequency Command)

4 — Master (Output Frequency)

5 — Master (Torque Reference)

6 — Master (Output Torque)

RS485 4-Wire Protocol Selection (TSB/ModBus)

Direct Access Number — F829

Program Communications Communication Settings

Parameter Type — Selection List

This parameter sets the communications protocol for ASD-to-ASD

Factory Default — Toshiba

Changeable During Run — Yes

communications.

 

Settings:

 

0 — Toshiba

 

1 — Modbus

 

 

 

Communications Option (DeviceNet/Profibus) Setting 1

Direct Access Number — F830

Program Communications Communication Settings

Parameter Type — Selection List

While using the DeviceNet/Profibus communications protocol, this parameter

Factory Default — 0

Changeable During Run — Yes

allows the user to select the read and write information communicated between

 

the ASD and the Host.

 

Read information may include the ASD fault status, ASD speed, ASD MAC

 

ID, etc. Write information may include Enable/Disable DeviceNet commands,

 

Forward run, ACC/DEC command, etc.

 

See the DeviceNet Option Instruction Manual (P/N 58683) for more

 

information on this parameter.

 

Settings:

 

0 – 7

 

H9 ASD Installation and Operation Manual

209