F854

F871

 

 

Communications Option Speed Switch Monitor DeviceNet/

Direct Access Number — F854

CC-Link

Parameter Type — Hardware Selectable

Program Communications Communication Settings

Factory Default — Option-Specific

This parameter is used in the setup of the communications network by reading

Changeable During Run — No

Minimum — 0

the hardware-specific settings of the option card being used with the ASD.

If using the DEV002Z Devicenet card, this parameter reads the hardware

Maximum — 255

 

switch SW300 setting of the Devicenet card. SW300 sets the baud rate and the

 

MAC address of the option card that is connected to a node of the

 

communications system.

 

See the DeviceNet Option Instruction Manual (P/N 58683) for more

 

information on this parameter or see the Instruction manual for the option being

 

used with the H9 ASD.

 

 

 

Block Write Data 1

Direct Access Number — F870

Program Communications Communication Settings

Parameter Type — Selection List

 

Factory Default — None

This parameter plays a role in the setup of the communications network by

Changeable During Run — Yes

establishing the type of data to be written to the ASD of the communications link.

The communications network includes other ASDs and Host/Control computers that monitor the status of the ASD(s), transfers commands, and loads or modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

0 — None

1 — FA00 (command 1)

2 — FA20 (command 2)

3 — FA01 (frequency)

4 — FA50 (TB output)

5 — FA51 (analog output)

Block Write Data 2

Direct Access Number — F871

Program Communications Communication Settings

Parameter Type — Selection List

This parameter plays a role in the setup of the communications network by

Factory Default — None

Changeable During Run — Yes

establishing the type of data to be written to the ASD of the communications

 

link.

 

The communications network includes other ASDs and Host/Control computers

 

that monitor the status of the ASD(s), transfers commands, and loads or

 

modifies the parameter settings of the ASD.

 

Changes made to this parameter require that the power be cycled (Off then On)

 

for the changes to take effect.

 

Settings:

 

0

— None

 

1

— FA00 (command 1)

 

2

— FA20 (command 2)

 

3

— FA01 (frequency)

 

4

— FA50 (TB output)

 

5

— FA51 (analog output)

 

H9 ASD Installation and Operation Manual