F264

F264

UP/DOWN Frequency (up) Response Time

No Path — Direct Access Only

This parameter functions in conjunction with the parameter settings of F265, F266, F267, F268, and F269. The purpose of these settings is to setup the ASD to allow an externally-supplied discrete input signal to control the output frequency of the ASD.

This method uses the discrete input terminal settings UP/DOWN Frequency (up) and UP/DOWN Frequency (down) to change the ASD speed. Activation of either terminal increases or decreases the output frequency at the Accel 1 or Decel 1 rates, respectively.

Depending on the Delay setting, the UP/DOWN Frequency (up/down) terminal may perform 1) the increase/decrease function for the duration of activation or 2) the UP/DOWN Frequency (up/down) terminal may act as a momentary contact that loads a new commanded frequency upon activation.

In either case, to activate-and-hold will continue the up or down function until reaching the Upper Limit Frequency or the Lower Limit Frequency, respectively. At which point further activation will be ignored.

See Figure 29 on pg. 130 for more information on the UP/DOWN Frequency function.

Setup Requirements

F003 — Selects the Command control source; set to Terminal Block.

F004 — Selects the Frequency Control Mode 1 control source; set to UP/DOWN Frequency.

F207 — Selects the Frequency Control Mode 2 control source: set to UP/DOWN Frequency if used.

Set one unused discrete input terminal to UP/DOWN Frequency (up) and one unused discrete input terminal to UP/DOWN Frequency (down).

F264 Sets the system-response delay to the initial activation of the discrete input terminal UP/DOWN Frequency (up). Also sets the response delay of subsequent terminal activations of the UP/DOWN Frequency (up) terminal during an activate-and-hold.

F265 Sets the frequency increase amount for each activation of the UP/ DOWN Frequency (up) terminal activation. The rate of the frequency increase is set at Acceleration Time 1 (F009).

F266 Sets the system-response delay to the initial activation of the discrete input terminal UP/DOWN Frequency (down). Also sets the activation delay of subsequent terminal activations of the UP/DOWN Frequency (down) terminal during an activate-and-hold.

F267 Sets the frequency decrease amount for each activation of the UP/ DOWN Frequency (down) terminal activation. The rate of the frequency decrease is set at Deceleration Time 1 (F010).

F268 At power up or after a reset, this parameter setting is used to provide a starting frequency for the UP/DOWN Frequency function.

F269 At power down while running, and when enabled, this parameter writes the running frequency into the F268 location and, upon a system restart, uses this setting as the startup frequency.

Provide a Run command (F or R). The motor will run at the F268 setting.

Direct Access Number — F264

Parameter Type — Numerical

Factory Default — 0.1

Changeable During Run — Yes

Minimum — 0.0

Maximum — 10.0

Units — Seconds

Up/Down Frequency (up) Mode

Up/Down Frequency (down) Mode

128

H9 ASD Installation and Operation Manual

Page 136