F511

F514

Deceleration Time 3

Program Special Accel/Decel #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go from the Maximum Frequency to 0.0 Hz for the #3 Deceleration profile.

The Accel/Decel pattern may be set using F502. The minimum Accel/Decel time may be set using F508.

Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads. Automatic Accel/Decel, Stall, and Ridethrough settings may lengthen the deceleration times.

Direct Access Number — F511

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Acceleration/Deceleration Pattern 3

Direct Access Number —

F512

Program Special Accel/Decel #1 – #4 Settings

Parameter Type — Selection List

This parameter enables a user-selected preprogrammed output profile that

Factory Default — Linear

 

Changeable During Run — Yes

controls the acceleration and deceleration pattern for the #3 Accel/Decel

 

 

parameter.

 

 

Settings:

 

 

0 — Linear

 

 

1 — S-Pattern 1

 

 

2 — S-Pattern 2

 

 

 

 

 

Acceleration/Deceleration Switching Frequency 2

Direct Access Number —

F513

Program Special Accel/Decel Special

Parameter Type — Numerical

This parameter sets the frequency at which the acceleration control is switched

Factory Default — 0.00

 

Changeable During Run — Yes

from the Accel #2 profile to the Accel #3 profile during a multiple-acceleration

 

 

profile configuration.

Minimum — 0.00

 

Maximum — Max. Freq. (F011)

Units — Hz

Acceleration Time 4

Program Special Accel/Decel #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go from 0.0 Hz to the Maximum Frequency for the #4 Acceleration profile. The Accel/Decel pattern may be set using F502. The minimum Accel/Decel time may be set using F508.

Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads. Automatic Accel/Decel, Stall, and Ridethrough settings may lengthen the acceleration times.

Direct Access Number — F514

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds