F265 |
| F269 | |
|
|
| |
UP/DOWN Frequency (up) Frequency Step | Direct Access Number — | F265 | |
No Path — Direct Access Only | Parameter Type — Numerical | ||
This parameter sets the frequency increase amount for each activation of the | Factory Default — 0.10 |
| |
Changeable During Run — Yes | |||
UP/DOWN Frequency (up) terminal activation. The rate of the frequency | |||
|
| ||
increase is set at Acceleration Time 1 (F009). | Minimum — 0.00 |
| |
See F264 for more information on this parameter. | Maximum — Max. Freq. (F011) | ||
Units — Hz |
| ||
|
| ||
|
|
| |
UP/DOWN Frequency (down) Response Time | Direct Access Number — | F266 | |
No Path — Direct Access Only | Parameter Type — Numerical | ||
This parameter sets the | Factory Default — 0.1 |
| |
Changeable During Run — Yes | |||
discrete input terminal UP/DOWN Frequency (down). Also sets the activation | |||
|
| ||
delay of subsequent terminal activations of the UP/DOWN Frequency (down) | Minimum — 0.0 |
| |
terminal during an | Maximum — 10.0 |
| |
|
| ||
See F264 for more information on this parameter. | Units — Seconds |
| |
|
| ||
|
|
| |
UP/DOWN Frequency (down) Frequency Step | Direct Access Number — | F267 | |
No Path — Direct Access Only | Parameter Type — Numerical | ||
F267 | Factory Default — 0.10 |
| |
Changeable During Run — Yes | |||
DOWN Frequency (down) terminal activation. The rate of the frequency | |||
|
| ||
decrease is set at Deceleration Time 1 (F010). | Minimum — 0.00 |
| |
See F264 for more information on this parameter. | Maximum — Max. Freq. (F011) | ||
| Units — Hz |
|
Initial UP/DOWN Frequency
No Path — Direct Access Only
At power up or after a reset, this parameter setting is used to provide a starting frequency for the UP/DOWN Frequency function.
See F269 for more information on this parameter setting.
Direct Access Number — F268
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Initial UP/DOWN Frequency Rewriting
No Path — Direct Access Only
At power down, and when enabled, this parameter writes the running frequency into the F268 location and, upon a system restart, uses this setting as the startup frequency.
Disable this parameter and set parameter F268 to the desired startup frequency if the same starting frequency is required at each startup.
Direct Access Number — F269
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Note: This parameter setting may be different at each startup when enabled.
Settings:
0 — Disabled
1 — Enabled (Overwrite F268 at Power Off or Reset)
H9 ASD Installation and Operation Manual | 129 |