Toshiba H9 operation manual F265 F269

Models: H9

1 289
Download 289 pages 12.38 Kb
Page 137
Image 137

F265

 

F269

 

 

 

UP/DOWN Frequency (up) Frequency Step

Direct Access Number —

F265

No Path — Direct Access Only

Parameter Type — Numerical

This parameter sets the frequency increase amount for each activation of the

Factory Default — 0.10

 

Changeable During Run — Yes

UP/DOWN Frequency (up) terminal activation. The rate of the frequency

 

 

increase is set at Acceleration Time 1 (F009).

Minimum — 0.00

 

See F264 for more information on this parameter.

Maximum — Max. Freq. (F011)

Units — Hz

 

 

 

 

 

 

UP/DOWN Frequency (down) Response Time

Direct Access Number —

F266

No Path — Direct Access Only

Parameter Type — Numerical

This parameter sets the system-response delay to the initial activation of the

Factory Default — 0.1

 

Changeable During Run — Yes

discrete input terminal UP/DOWN Frequency (down). Also sets the activation

 

 

delay of subsequent terminal activations of the UP/DOWN Frequency (down)

Minimum — 0.0

 

terminal during an activate-and-hold.

Maximum — 10.0

 

 

 

See F264 for more information on this parameter.

Units — Seconds

 

 

 

 

 

 

UP/DOWN Frequency (down) Frequency Step

Direct Access Number —

F267

No Path — Direct Access Only

Parameter Type — Numerical

F267 —Sets the frequency decrease amount for each activation of the UP/

Factory Default — 0.10

 

Changeable During Run — Yes

DOWN Frequency (down) terminal activation. The rate of the frequency

 

 

decrease is set at Deceleration Time 1 (F010).

Minimum — 0.00

 

See F264 for more information on this parameter.

Maximum — Max. Freq. (F011)

 

Units — Hz

 

Initial UP/DOWN Frequency

No Path — Direct Access Only

At power up or after a reset, this parameter setting is used to provide a starting frequency for the UP/DOWN Frequency function.

See F269 for more information on this parameter setting.

Direct Access Number — F268

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — Lower Limit (F013)

Maximum — Upper Limit (F012)

Units — Hz

Initial UP/DOWN Frequency Rewriting

No Path — Direct Access Only

At power down, and when enabled, this parameter writes the running frequency into the F268 location and, upon a system restart, uses this setting as the startup frequency.

Disable this parameter and set parameter F268 to the desired startup frequency if the same starting frequency is required at each startup.

Direct Access Number — F269

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — Yes

Note: This parameter setting may be different at each startup when enabled.

Settings:

0 — Disabled

1 — Enabled (Overwrite F268 at Power Off or Reset)

H9 ASD Installation and Operation Manual

129

Page 137
Image 137
Toshiba H9 operation manual F265 F269