Table 8. Terminal assignments and the associated My Function Input Setting (Input Function Target) and Parameter Setting numbers for the FLA/B/C, O1A/O1B (OUT1), O2A/O2B (OUT2), OUT3OUT6, R1R4terminals.

Discrete Output Terminal Assignment Selections

 

Input

Param

Function

Input

Param

Function

 

Setting

Setting

Setting

Setting

 

 

 

 

 

 

 

 

 

 

1000

0

Lower Limit Frequency

1086

86

Error Code Output 4

 

 

 

 

 

 

1002

2

Upper Limit Frequency

1088

88

Error Code Output 5

 

 

 

 

 

 

1004

4

Low Speed Signal

1090

90

Error Code Output 6

 

 

 

 

 

 

1006

6

Acceleration/Deceleration Completion

1092

92

Specified Data Output 1

 

 

 

 

 

 

1008

8

Speed Reach Signal

1094

94

Specified Data Output 2

 

 

 

 

 

 

1010

10

Failure FL (All trips)

1096

96

Specified Data Output 3

 

 

 

 

 

 

1012

12

Failure FL (Except EF, OCL, EPHO, OL2)

1098

98

Specified Data Output 4

 

 

 

 

 

 

1014

14

Overcurrent (OC) Alarm

1100

100

Specified Data Output 5

 

 

 

 

 

 

1016

16

ASD Overload (OL1) Alarm

1102

102

Specified Data Output 6

 

 

 

 

 

 

1018

18

Motor Overload (OL2) Alarm

1104

104

Specified Data Output 7

 

 

 

 

 

 

1020

20

Overheat Alarm

1106

106

Light Load

 

 

 

 

 

 

1022

22

Overvoltage Alarm

1108

108

Heavy Load

 

 

 

 

 

 

1024

24

Main Circuit (MOFF) Undervoltage Alarm

1110

110

Positive Torque Limit

 

 

 

 

 

 

1026

26

Low Current Alarm

1112

112

Negative Torque Limit

 

 

 

 

 

 

1028

28

Overtorque Alarm

1114

114

External Rush Suppression Relay Activated

 

 

 

 

 

 

1030

30

DBR Overload Alarm

1118

118

Completion of Stop Positioning

 

 

 

 

 

 

1032

32

Emergency Off Active

1120

120

L-STOP

 

 

 

 

 

 

1034

34

Retry Active

1122

122

Power Failure Synchronized Operation

 

 

 

 

 

 

1036

36

Pattern Operation Switching Output

1124

124

Traverse in Progress

 

 

 

 

 

 

1038

38

PID Deviation Limit

1126

126

Traverse Deceleration Active

 

 

 

 

 

 

1040

40

Run/Stop

1128

128

Part Replacement Alarm

 

 

 

 

 

 

1042

42

Serious Failure (OCA, OCL, EF, phase failure, etc.)

1130

130

Overtorque Alarm

 

 

 

 

 

 

1044

44

Light failure (OL, OC1, 2, 3, OP)

1132

132

Frequency Command ½ Selection

 

 

 

 

 

 

1046

46

Commercial Power/ASD Switching Output 1

1134

134

Failure FL (Except Emergency Off)

 

 

 

 

 

 

1048

48

Commercial power/ASD switching Output 2

1222

222

My Function Output 1

 

 

 

 

 

 

1050

50

Cooling Fan ON/OFF

1224

224

My Function Output 2

 

 

 

 

 

 

1052

52

Jogging Operation Active (jog run active)

1226

226

My Function Output 3

 

 

 

 

 

 

1054

54

Panel/Terminal Board Operation Switching

1228

228

My Function Output 4

 

 

 

 

 

 

1056

56

Cumulative Run-time Alarm

1230

230

My Function Output 5

 

 

 

 

 

 

1058

58

ProfiBus/DeviceNet/CC-Link Communication Error

1232

232

My Function Output 6

 

 

 

 

 

 

1060

60

Forward/Reverse Switching

1234

234

My Function Output 7

 

 

 

 

 

 

1062

62

Ready for Operation 1

1236

236

My Function Output 8

 

 

 

 

 

 

1064

64

Ready for Operation 2

1238

238

My Function Output 9

 

 

 

 

 

 

1068

68

Brake Release (BR)

1240

240

My Function Output 10

 

 

 

 

 

 

1070

70

Alarm Status Active

1242

242

My Function Output 11

 

 

 

 

 

 

1072

72

Forward Speed Limit (torque control)

1244

244

My Function Output 12

 

 

 

 

 

 

1074

74

Reverse Speed Limit (torque control)

1246

246

My Function Output 13

 

 

 

 

 

 

1076

76

ASD Healthy Output

1248

248

My Function Output 14

 

 

 

 

 

 

1078

78

RS485 Communication Error

1250

250

My Function Output 15

 

 

 

 

 

 

1080

80

Error Code Output 1

1252

252

My Function Output 16

 

 

 

 

 

 

1082

82

Error Code Output 2

1254

254

Always OFF

 

 

 

 

 

 

1084

84

Error Code Output 3

 

 

 

 

 

 

 

 

 

 

 

Note:

Only positive logic is available for the listed parameters.

 

 

 

H9 ASD Installation and Operation Manual

241

Page 249
Image 249
Toshiba H9 operation manual Input Param Function, Setting