F959

F962

 

 

Analog Input Function Target 11

Direct Access Number — F959

Program My Function My Function Analog

Parameter Type — Selection List

This parameter plays a role in the setup of the My Function feature by

Factory Default — 0 (Disabled)

Changeable During Run — Yes

selecting the functionality of the programmable Analog Input Function Target

 

11 terminal.

 

The function selected at F961 may be adjusted using the input analog control

 

signal selected here.

 

Settings:

 

0

— Disabled (None)

 

1

— V/I

 

2

— RR

 

3

— RX

 

4— Optional RX2+, RX2-

5— Optional V/I

Analog Function Assigned Object 11

Direct Access Number — F961

Program My Function My Function Analog

Parameter Type — Selection List

This parameter plays a role in the setup of the My Function feature by

Factory Default — 0 (Disabled)

Changeable During Run — Yes

selecting the functionality to which the adjustment of F959 is applied.

 

Settings:

 

0

— Disabled (None)

 

1

— Acceleration Rate

 

2

— Upper Limit Frequency

 

3

— Acceleration Multiplication Factor

 

4

— Deceleration Multiplication Factor

 

5

— Manual Torque Boost

 

6— Over Current Stall (F601)

7— Thermal Protection

8— Speed Loop P Gain (F460)

9— Drooping Gain (F320)

10— PID P Gain (F362)

See the My Function Instruction Manual (P/N 58692) for a complete description of the setup requirements and operational information of the Analog Function Assigned Object parameter.

Analog Input Function Target 21

Direct Access Number — F962

Program My Function My Function Analog

Parameter Type — Selection List

This parameter plays a role in the setup of the My Function feature by

Factory Default — 0 (Disabled)

Changeable During Run — Yes

selecting the functionality of the programmable Analog Input Function Target

 

21 terminal.

 

The function selected at F964 may be adjusted using the input analog control

 

signal selected here.

 

Settings:

 

0

— Disabled (None)

 

1

— V/I

 

2

— RR

 

3

— RX

 

4— Optional RX2+, RX2-

5— Optional V/I

228

H9 ASD Installation and Operation Manual

Page 236
Image 236
Toshiba H9 operation manual F959 F962, Analog Input Function Target, Analog Function Assigned Object