Direct Access Parameter Information
The H9 ASD has the ability to allow the user direct access to the motor control functions. There are two ways in which the
The Program mode allows the user to develop an
Note: Parameter selections are preceded by the number used to select an item if using communications to write to a parameter location in memory (i.e., F000 ⇒
Note: The setup procedures included within this section may require a Reset before performing the procedure.
Note: Communications setting changes will require that the power be removed and then
Direct Access Parameters/Numbers
Automatic Acceleration/Deceleration
Program ⇒ Fundamental ⇒ Accel/Decel #1 Settings
This parameter is used to allow the ASD to adjust the acceleration and deceleration rates in accordance with the applied load automatically.
The adjusted acceleration and deceleration times range from 12.5% to 800% of the programmed values for Acceleration Time #1 (F009) and Deceleration
Time #1 (F010).
Settings:
0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC Only
Direct Access Number — F000
Parameter Type — Selection List
Factory Default — Manual
Changeable During Run — No
Note: The motor and the load must be connected prior to selecting Automatic Acceleration/Deceleration.
Automatic Torque Boost
Program ⇒ Fundamental ⇒ Motor Set #1
This parameter allows the ASD to adjust the output torque in accordance with the applied load automatically. When enabled Autotuning is performed — the motor should be connected before performing an Autotune.
Settings:
0 — Disabled
1 — Automatic Torque Boost + Autotuning
2 — Sensorless Vector Control + Autotuning
Direct Access Number — F001
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
76 | H9 ASD Installation and Operation Manual |