F502

F502

Acc/Dec Pattern 1

Program Special Accel/Decel #1 – #4 Settings

This parameter enables a user-selected preprogrammed output profile that controls the acceleration and deceleration pattern for the #1 Accel/Decel parameter.

Settings:

0 — Linear

1S-Pattern 1

2S-Pattern 2

The figures below provide a profile of the available accel/decel patterns.

Linear acceleration and deceleration is the default pattern and is used on most applications.

S-pattern 1 is used for applications that require quick acceleration and deceleration. This setting is also popular for applications that require shock absorption at the start of acceleration or deceleration.

S-pattern 2 decreases the rate of change above the base frequency.

Direct Access Number — F502

Parameter Type — Selection List

Factory Default — Linear

Changeable During Run — Yes

H9 ASD Installation and Operation Manual

165

Page 173
Image 173
Toshiba H9 operation manual Acc/Dec Pattern, Program ⇒ Special ⇒ Accel/Decel #1 #4 Settings, Direct Access Number F502