F802

 

F804

 

 

 

ASD Number

Direct Access Number —

F802

Program Communications Communication Settings

Parameter Type — Numerical

This parameter plays a role in the setup of the communications network by

Factory Default — 0

 

 

 

assigning an identification (ID) number to each ASD in the communications

Changeable During Run — Yes

network.

Minimum — 0

 

 

 

The communications network includes other ASDs and Host/Control computers

Maximum — 247

 

that monitor the status of the ASD(s), transfers commands, and loads or

 

 

 

modifies the parameter settings of the ASD.

 

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

 

 

 

Communications Time Out Time (RS485 2- and 4-wire)

Direct Access Number —

F803

Program Communications Communication Settings

Parameter Type — Numerical

This parameter plays a role in the setup of the communications network by

Factory Default — 0 (Off)

 

 

 

setting the time that no activity may exist over the communications link before

Changeable During Run — Yes

the link is severed (Time Out).

Minimum — 0 (Off)

 

 

 

The communications network includes other ASDs and Host/Control computers

Maximum — 100

 

that monitor the status of the ASD(s), transfers commands, and loads or

 

Units — Seconds

 

modifies the parameter settings of the ASD.

 

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Communications Time-Out Action (RS485 2- and 4-wire)

Program Communications Communication Settings

This parameter plays a role in the setup of the communications network by determining the action to be taken in the event of a time-out (Time-Out Action).

The communications network includes other ASDs and Host/Control computers that monitor the status of the ASD(s), transfers commands, and loads or modifies the parameter settings of the drive.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

(settings are for 2-wire/4-wire)

0 — No Action/No Action

1 — Alarm/No Action

2 — Trip/No Action

3 — No Action/Alarm

4 — Alarm/Alarm

5 — Trip/Alarm

6 — No Action/Trip

7 — Alarm/Trip

8 — Trip/Trip

Direct Access Number — F804

Parameter Type — Selection List

Factory Default — Trip/Trip

Changeable During Run — Yes

H9 ASD Installation and Operation Manual

205

Page 213
Image 213
Toshiba H9 operation manual F802 F804, ASD Number, Communications Time Out Time RS485 2- and 4-wire