H9 ASD Installation and Operation Manual 193

Adding Input Selection

Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the ex ternal
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The se lected
input is used as a modifier of th e pr ogrammed Output Frequency.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 (2-wire)
6 — RS485 (4-wire)
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (terminal board)
11 — Pulse Input (option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (option)
Direct Access Number — F660
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes

Multiplying Inpu t Selection

Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the ex ternal
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The se lected
input is used as a multiplier of the pr og r am me d Output Frequency.
If operating using the LED Keypad Option and Setting is selected, the value
entered at F729 is used as the multiplier.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — F729 (setting)
5 — RX2 Option (AI1)
Direct Access Number — F661
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F660 F661