H9 ASD Installation and Operation Manual 85

Automatic Function Selection

Program Utilities Display Parameters
This parameter setting is used to co n fi gu r e m u lti ple parameters with the settin g
of only one parameter. From the selection below multiple parameters may be
set as indicated in the table.
Once set, the selected configurat ion is placed in effect and remains in effect
until this parameter is ch a nged or the individual se ttings are changed.
Set this parameter to Disable to s et these paramete rs individually.
Note: After performing the desired selection the EOI display returns to
Disabled though the selected function has been carried out (i.e.,
without this, if selection 1 is performed, F004 and F207 would
hold the RR terminal setting regardless of atte mpt s to cha nge the
settings individually).
Settings:
0 — Disabled
1 — RR
2 — V/I
3 — RR or V/I Switched via Terminal Boar d
4 — Keypad = Frequency/Terminal Board = Command
5 — Keypad = Frequency and Command
Direct Access Number F040
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
User Settings
Related
Parameters Default
Settings 0-Disable 1-RR 2-V/I 3-RR or V/I
via TB
4-Keypad/
Freq.
CMD/TB
5-Keypad
Freq/CMD
CMOD
F003 Termina l
Board N/C Termin al
Board Keypad
FMOD1
F004 RR N/C RR N/C RR Keypad
S3 Terminal
F117 Preset
Speed 3 N/C Fr eq. R e f.
Priority N/C
Freq.
Priority
F200
Termin al
Board N/C Terminal Board
V/I Setup
F201 0.0% N/C 20.0% N /C
FMOD2
F207 V/I N/C RR V/I Keypad
N/C = No Change — the setting re mains as it was before setting para meter F040.
F040 F040