F228 | F228 |
BIN Input Point 1 Setting
Program ⇒ Frequency ⇒ Speed Reference Setpoints
This parameter is used to set the gain and bias of the BIN input terminals when the BIN terminals are used as the control input while operating in the Speed Control mode.
The discrete input terminals of the Terminal Board are used as the BIN terminals.
BIN Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input at the BIN input terminals:
•Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode 1 ⇒ Binary/BCD.
•Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode Selection ⇒ Terminal Block.
•Program ⇒ Terminal ⇒ Input Terminals; select and set the desired discrete input terminals to Binary Bit(s) 0 – 7 (or 0 – MSB). The binary input word will control the speed of the motor.
•Program ⇒ Terminal ⇒ Input Terminals; select and set a discrete input terminal to Binary Data Write. Activation of the Binary Data Write terminal will transfer the status of the Binary Bit(s) 0 – 7 (or 0 – MSB) to the control board for speed control.
Speed Control
Perform the following setup to allow the system to perform Speed control from the BIN input terminals:
•Set BIN Input Point 1 Frequency (F229).
•Set the BIN input value (% of 255D) (F228) that represents BIN Input Point 1 Frequency.
•Set BIN Input Point 2 Frequency (F231).
•Set the BIN input value (% of 255D) (F230) that represents BIN Input Point 2 Frequency.
•Provide a Run command (F and/or R).
Note: 255D is the decimal equivalent of the
Once set, as the BIN input signal changes are transferred to the control board, the output frequency of the ASD will vary in accordance with the above settings.
This parameter sets BIN Input Point 1 Setting and is entered as 0% to 100% of the of the range represented by the BIN binary input word 11111111 (255D) or the binary bit(s) 0 – MSB.
Direct Access Number — F228
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Frequency Settings
120 | H9 ASD Installation and Operation Manual |