F234

F235

PG Input Point 1 Setting

Program Frequency Speed Reference Setpoints

This parameter is used to set the gain and bias of the PG input terminal of the option board when a shaft-mounted encoder is used as the control input while operating in the Speed Control mode.

Note: See Instruction Manual P/N 58687 for more information on the

PG Option Board.

PG Input Speed Control Setup

Perform the following setup to allow the system to receive Speed control input at the PG input terminal:

Program Fundamental Standard Mode Selection Frequency Mode 1 Pulse Input (option).

Program Fundamental Standard Mode Selection Command Mode Selection (any setting).

Provide a Run command (F and/or R).

Speed Control

Perform the following setup to allow the system to perform Speed control from the PG input terminals:

Set PG Point 1 Frequency (F235).

Set the PG input value (F234) that represents PG Point 1 Frequency.

Set PG Point 2 Frequency (F237).

Set the PG input value (F236) that represents PG Point 2 Frequency.

Once set, as the PG input pulse count rate changes, the output frequency of the drive will vary in accordance with the above settings.

This parameter sets the PG input pulse count that represents Reference Setpoint #1 (frequency). The range of values for this parameter is 0% to 100% of the PG input pulse count range.

Direct Access Number — F234

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0

Maximum — 100.0

Units — %

Frequency Settings

Note: Further application-specific PG settings may be performed from the following path: Program Feedback PG Settings.

PG Input Point 1 Frequency

Program Frequency Speed Reference Setpoints

This parameter is used to set the speed of the PG input terminals when the PG terminal is used as the control input.

This parameter sets PG Point 1 Frequency and is the frequency that is associated with the setting of PG Point 1 Setting.

See PG Point 1 Setting for further information on this setting.

Direct Access Number — F235

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (F011)

Units — Hz

122

H9 ASD Installation and Operation Manual

Page 130