Cable/Terminal/Torque Specifications

Installation should conform to the 2005 National Electrical Code Article 110 (NEC) (Requirements for Electrical Installations), all regulations of the Occupational Safety and Health Administration, and any other applicable national, regional, or industry codes and standards.

Note: The following ratings are guidelines and shall not be the sole determining factor of the lug or wire size used with the H9 ASD. Application-specific applicables, wire insulation type, conductor material, and local and regional regulations are but a few of the considerations when selecting the actual lug and wire type to be used with the H9 ASD.

Note: Cable/Terminal specifications are based on the rated current of the H9 ASD and Do Not include the 10% Service Factor.

Note: Use only 75° C copper wire/cable for motor and power connections.

For further installation information see the section titled Installation and Connections on pg. 14.

Table 20. 230-Volt H9 ASD Cable/Terminal/Torque Specifications.

 

 

Wire/Cable Size

Lug Size Range

Terminal

 

 

 

 

 

Board

 

Torque

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

MCP Rating

 

 

AWG or kcmil

 

 

 

 

 

Number

 

 

 

 

 

 

 

(Amps)

 

 

 

 

 

 

 

 

 

VT130H9U

Input/Output Power

Wire-Size/Lug-Capacity for

TB1 – 4

 

3Ø-Input

3Ø-Output

 

 

 

 

Input/Output Power

Terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended

Maximum

3Ø-Input

 

3Ø-Output

 

In-Lbs./Nm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2035

30

14

10

14 to 8

 

 

 

11.5/1.3

 

 

 

 

 

 

 

2055

30

10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2080

50

8

8

12 to 8

 

 

 

17.7/2.0

 

 

 

 

 

 

 

2110

50

8

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2160

75

6

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2220

100

4

3

8 to 3

 

20

 

21/2.4

 

 

 

 

 

 

 

 

 

 

2270

125

3

3

 

 

 

 

 

 

 

 

 

(3-core shield)

 

 

 

 

 

 

 

 

 

 

 

 

2330

150

2

2

12 to 1/0

 

4 to 1/0

5.3/0.6

 

50/5.7

53/6

 

 

 

 

 

 

 

 

 

 

2400

175

1/0

4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

200

2/0

4/0

6 to 250

 

2 to 300

 

 

275/31

168/19

 

 

 

 

 

 

 

2600

250

3/0

4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2750

300

4/0

4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

210K

400

*3/0

*1/0

6 to 250

 

 

275/31

 

 

 

 

 

 

212K

500

*250

*250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: (*) Indicates that the item is one of a set of two parallel cables.

H9 ASD Installation and Operation Manual

265

Page 273
Image 273
Toshiba H9 Cable/Terminal/Torque Specifications, Wire/Cable Size Lug Size Range Terminal Board Torque, Model