EOI Command Mode
The EOI Command mode is accessed by pressing the ESC key from the Frequency Command screen.
The control settings of the EOI Command menu are effective for EOI control only.
The EOI Command mode provides quick access to the following menu parameters:
Direction — Forward or Reverse.
Stop Pattern — The Decel Stop or Coast Stop settings determines the method used to stop the motor when using the StopReset key of the EOI. The Decel Stop setting enables the Dynamic Braking system setup at F304 or the DC Injection Braking system setup at F250, F251, and F252. The Coast Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Note: The Stop Pattern setting has no effect on the Emergency Off settings of F603.
V/f Group — 1 of 4 V/f profiles may be selected and run. Each V/f profile is comprised of 4 user settings: Base Frequency, Base Frequency Voltage, Manual Torque Boost, and Electronic Thermal Protection. Expanded descriptions of these parameters may be found in the section titled Direct Access Parameter Information on pg. 76.
Accel/Decel Group — 1 of 4 Accel/Decel profiles may be selected and run. Each of the Accel/ Decel profiles is comprised of 3 user settings: Acceleration, Deceleration, and Pattern. Expanded descriptions of these parameters may be found in the section titled Direct Access Parameter Information on pg. 76 (or see F009).
Feedback in Panel Mode — This feature enables or disables the PID feedback function.
Torque Limit Group — This parameter is used to select 1 of 4 preset positive torque limits to apply to the active motor (of a multiple motor configuration). The settings of profiles 1 – 4 may be setup at F441, F444, F446, and F448, respectively.
42 | H9 ASD Installation and Operation Manual |