Jog Stop Pattern
Program ⇒ Frequency ⇒ Jog Settings
This parameter sets the stopping method used while operating in the Jog mode.
Note: This parameter setting is used for the Jog operation only. The Emergency Off stopping method setting of parameter F603 has priority over this setting and changes made here do not affect the function or setting of parameter F603.
Settings:
0 — Deceleration Stop
1 — Coast Stop
2 — DC Injection Braking Stop
Direct Access Number — F261
Parameter Type — Selection List
Factory Default — Deceleration Stop
Changeable During Run — Yes
Panel Operation Jog Mode
Program ⇒ Frequency ⇒ Jog Settings
This parameter enables the Jog command to be received from the EOI. When disabled the Jog command received from the EOI is ignored.
Jog commands may also be received from the Terminal Board. Priority as to which is allowed to override the other is selected at F106.
The priority selection at F106 enables the selected source for Jog control and disables the other. The F106 setting overrides this parameter setting.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F262
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
H9 ASD Installation and Operation Manual | 127 |