198 H9 ASD Installation and Operation Manual

MON 1 Bias Adjustment

Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON1 terminal.
Set the assigned function of parameter F672 to zero and then set this parameter
to a zero output.
See parameter F672 for more information on this set ting.
Direct Access Number — F690
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %

MON 2 Voltage/Current Output Switching

Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON2 output
terminal.
See parameter F674 for more information on this set ting.
Settings
0 — -10V – +10V
1 — 0 – 10V
2 — 0 – 20 mA
Direct Access Number — F691
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — Yes

MON 2 Output Gradient Characteristic

Program Terminal Analog Output Terminals
This parameter sets th e output response polar ity of the MON2 output terminal.
The MON2 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter F672 for more information on this set ting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F692
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes

MON 2 Bias Adjustment

Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON2 terminal.
Set the assigned function of parameter F674 to zero and then set this parameter
to a zero output.
See parameter F674 for more information on this set ting.
Direct Access Number — F693
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %

Parameter Write Lockout

Program Utilities Prohibition
This parameter Enables/Disables the Run and Stop keys.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number — F700
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
F690 F700