MON 1 Bias Adjustment | Direct Access Number — | F690 | |
Program ⇒ Terminal ⇒ Analog Output Terminals | Parameter Type — Numerical | ||
This parameter setting is used to ensure that a | Factory Default — 0.0 |
| |
Changeable During Run — Yes | |||
|
| ||
Set the assigned function of parameter F672 to zero and then set this parameter | Minimum — |
| |
|
| ||
to a zero output. | Maximum — 100.0 |
| |
See parameter F672 for more information on this setting. | Units — % |
| |
|
|
| |
MON 2 Voltage/Current Output Switching | Direct Access Number — | F691 | |
Program ⇒ Terminal ⇒ Analog Output Terminals | Parameter Type — Selection List | ||
This parameter is used to set the output signal type of the MON2 output | Factory Default — 0 – 10V |
| |
Changeable During Run — Yes | |||
terminal. | |||
|
| ||
See parameter F674 for more information on this setting. |
|
| |
Settings |
|
| |
0 — |
|
| |
1 — 0 – 10V |
|
| |
2 — 0 – 20 mA |
|
| |
|
|
| |
MON 2 Output Gradient Characteristic | Direct Access Number — | F692 | |
Program ⇒ Terminal ⇒ Analog Output Terminals | Parameter Type — Selection List | ||
This parameter sets the output response polarity of the MON2 output terminal. | Factory Default — Plus |
| |
Changeable During Run — Yes | |||
The MON2 output terminal response may be set to respond inversely | |||
|
| ||
directly (+) to the input signal. |
|
| |
See parameter F672 for more information on this setting. |
|
| |
Settings: |
|
| |
0 — Minus (Negative Gradient) |
|
| |
1 — Plus (Positive Gradient) |
|
| |
|
|
| |
MON 2 Bias Adjustment | Direct Access Number — | F693 | |
Program ⇒ Terminal ⇒ Analog Output Terminals | Parameter Type — Numerical | ||
This parameter setting is used to ensure that a | Factory Default — 0.0 |
| |
Changeable During Run — Yes | |||
|
| ||
Set the assigned function of parameter F674 to zero and then set this parameter | Minimum — |
| |
|
| ||
to a zero output. | Maximum — 100.0 |
| |
See parameter F674 for more information on this setting. | Units — % |
| |
|
|
| |
Parameter Write Lockout | Direct Access Number — | F700 | |
Program ⇒ Utilities ⇒ Prohibition | Parameter Type — Selection List | ||
| Factory Default — Enabled |
|
This parameter Enables/Disables the Run and Stop keys.
Settings:
0 — Enabled
1 — Disabled
Changeable During Run — Yes