MON 1 Bias Adjustment

Direct Access Number —

F690

Program Terminal Analog Output Terminals

Parameter Type — Numerical

This parameter setting is used to ensure that a zero-level input signal produces a

Factory Default — 0.0

 

Changeable During Run — Yes

zero-level output at the MON1 terminal.

 

 

Set the assigned function of parameter F672 to zero and then set this parameter

Minimum — -10.0

 

 

 

to a zero output.

Maximum — 100.0

 

See parameter F672 for more information on this setting.

Units — %

 

 

 

 

MON 2 Voltage/Current Output Switching

Direct Access Number —

F691

Program Terminal Analog Output Terminals

Parameter Type — Selection List

This parameter is used to set the output signal type of the MON2 output

Factory Default — 0 – 10V

 

Changeable During Run — Yes

terminal.

 

 

See parameter F674 for more information on this setting.

 

 

Settings

 

 

0 — -10V – +10V

 

 

1 — 0 – 10V

 

 

2 — 0 – 20 mA

 

 

 

 

 

MON 2 Output Gradient Characteristic

Direct Access Number —

F692

Program Terminal Analog Output Terminals

Parameter Type — Selection List

This parameter sets the output response polarity of the MON2 output terminal.

Factory Default — Plus

 

Changeable During Run — Yes

The MON2 output terminal response may be set to respond inversely (-) or

 

 

directly (+) to the input signal.

 

 

See parameter F672 for more information on this setting.

 

 

Settings:

 

 

0 — Minus (Negative Gradient)

 

 

1 — Plus (Positive Gradient)

 

 

 

 

 

MON 2 Bias Adjustment

Direct Access Number —

F693

Program Terminal Analog Output Terminals

Parameter Type — Numerical

This parameter setting is used to ensure that a zero-level input signal produces a

Factory Default — 0.0

 

Changeable During Run — Yes

zero-level output at the MON2 terminal.

 

 

Set the assigned function of parameter F674 to zero and then set this parameter

Minimum — -10.0

 

 

 

to a zero output.

Maximum — 100.0

 

See parameter F674 for more information on this setting.

Units — %

 

 

 

 

Parameter Write Lockout

Direct Access Number —

F700

Program Utilities Prohibition

Parameter Type — Selection List

 

Factory Default — Enabled

 

This parameter Enables/Disables the Run and Stop keys.

Settings:

0 — Enabled

1 — Disabled

Changeable During Run — Yes