F193

 

F197

 

 

 

 

 

V/f Five-Point Setting Voltage 2

Direct Access Number —

F193

 

Program Special V/f Five-Point Setting

Parameter Type — Numerical

 

The V/f Five-Point Setting Voltage 2 establishes the output voltage level that

Factory Default — 0.0

 

 

Changeable During Run — No

 

is to be associated with the frequency setting of F192 (V/f Five-Point Setting

 

 

 

 

Frequency 2).

Minimum — 0.0

 

 

The F701 parameter setting will determine if the selection for this parameter

Maximum — 100.0

 

 

appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.

Units — V or % (F701)

 

 

The default setting is %.

 

 

 

See F190 and F191 for additional information on this setting.

 

 

 

 

 

 

 

V/f Five-Point Setting Frequency 3

Direct Access Number —

F194

 

Program Special V/f Five-Point Setting

Parameter Type — Numerical

 

The Custom V/f Five-Point Setting Frequency 3 sets the frequency to be

Factory Default — 0.00

 

 

Changeable During Run — No

 

associated with the voltage setting of parameter F195 (V/f Five-Point Setting

 

 

 

 

Voltage 3).

Minimum — 0.00

 

 

See F190 and F191 for additional information on this setting.

Maximum — Max. Freq. (F011)

 

 

Units — Hz

 

 

 

 

 

 

V/f Five-Point Setting Voltage 3

Direct Access Number —

F195

 

Program Special V/f Five-Point Setting

Parameter Type — Numerical

 

The V/f Five-Point Setting Voltage 3 establishes the output voltage level that

Factory Default — 0.0

 

 

Changeable During Run — No

 

is to be associated with the frequency setting of F194 (V/f Five-Point Setting

 

 

 

 

Frequency 3).

Minimum — 0.0

 

 

The F701 parameter setting will determine if the selection for this parameter

Maximum — 100.0

 

 

appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.

Units — V or % (F701)

 

 

The default setting is %.

 

 

 

See F190 and F191 for additional information on this setting.

 

 

 

 

 

 

 

V/f Five-Point Setting Frequency 4

Direct Access Number —

F196

 

Program Special V/f Five-Point Setting

Parameter Type — Numerical

 

The Custom V/f Five-Point Setting Frequency 4 sets the frequency to be

Factory Default — 0.00

 

 

Changeable During Run — No

 

associated with the voltage setting of parameter F197 (V/f Five-Point Setting

 

 

 

 

Voltage 4).

Minimum — 0.00

 

 

See F190 and F191 for additional information on this setting.

Maximum — Max. Freq. (F011)

 

 

Units — Hz

 

V/f Five-Point Setting Voltage 4

Program Special V/f Five-Point Setting

The V/f Five-Point Setting Voltage 4 establishes the output voltage level that is to be associated with the frequency setting of F196 (V/f Five-Point Setting

Frequency 4).

The F701 parameter setting will determine if the selection for this parameter appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.

The default setting is %.

See F190 and F191 for additional information on this setting.

Direct Access Number — F197

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — No

Minimum — 0.0

Maximum — 100.0

Units — V or % (F701)

H9 ASD Installation and Operation Manual

103

Page 111
Image 111
Toshiba H9 operation manual F193 F197