V/f Five-Point Setting Voltage 2

Program Special V/f Five-Point Setting
The V/f Five-Point Setting Vo ltage 2 establishes the output voltage level that
is to be associated with the frequ ency setting of F192 (V/f Five-Point Setting
Frequency 2).
The F701 parameter setting will determine if the sel ec t i o n fo r th is par a m et er
appears in the form of a Vo ltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)

V/f Five-Point Setting Frequency 3

Program Special V/f Five-Point Setting
The Custom V/f Five-Point Setting Frequency 3 sets the frequency to be
associated with the voltage setting of parameter F195 (V/f Five-Point Setting
Volt age 3).
See F190 and F191 for additional information on this setting.
Direct Access Number F194
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz

V/f Five-Point Setting Voltage 3

Program Special V/f Five-Point Setting
The V/f Five-Point Setting Vo ltage 3 establishes the output voltage level that
is to be associated with the frequ ency setting of F194 (V/f Five-Point Setting
Frequency 3).
The F701 parameter setting will determine if the sel ec t i o n fo r th is par a m et er
appears in the form of a Vo ltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number F195
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)

V/f Five-Point Setting Frequency 4

Program Special V/f Five-Point Setting
The Custom V/f Five-Point Setting Frequency 4 sets the frequency to be
associated with the voltage setting of parameter F197 (V/f Five-Point Setting
Volt age 4).
See F190 and F191 for additional information on this setting.
Direct Access Number F196
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz

V/f Five-Point Setting Voltage 4

Program Special V/f Five-Point Setting
The V/f Five-Point Setting Vo ltage 4 establishes the output voltage level that
is to be associated with the frequ ency setting of F196 (V/f Five-Point Setting
Frequency 4).
The F701 parameter setting will determine if the sel ec t i o n fo r th is par a m et er
appears in the form of a Vo ltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number F197
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)