230 H9 ASD Installation and Operation Manual

Monitor Output Function 21

Program My Function My Function Monitor
This parameter plays a role in the setup of th e My Function feature by
establishing the function that is to be recor d ed and output as the Peak,
Minimum, or Average value as selected at parameter F968.
Select the Monitor Display Input Setting number from Table 10 on pg. 243 to
output the corresponding function.
Use the Communication Number if operating usin g communications.
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the
Monitor Output Func tion parameter.
Direct Access Number — F967
Parameter Type — Selection List
Factory Default — 2000
Changeable During Run — Yes

Monitor Output Function Command 21

Program My Function My Function Monitor
This parameter plays a ro le in the setup of the My Function feature by allowing
the user to select the Peak, Minimum, or Normal (Avg.) value of the
parameter F967 selection to be recorded and output as a monitored functio n.
Settings:
0 — Normal
1 — Peak
2 — Minimum
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the
Monitor Output Func tion parameter.
Direct Access Number — F968
Parameter Type — Selection List
Factory Default — Normal
Changeable During Run — Yes

Monitor Output Function 31

Program My Function My Function Monitor
This parameter plays a role in the setup of th e My Function feature by
establishing the function that is to be recor d ed and output as the Peak,
Minimum, or Average value as selected at parameter F970.
Select the Monitor Display Input Setting number from Table 10 on pg. 243 to
output the corresponding function.
Use the Communication Number if operating usin g communications.
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the
Monitor Output Func tion parameter.
Direct Access Number — F969
Parameter Type — Selection List
Factory Default — 2000
Changeable During Run — Yes
F967 F969