F342 | F346 | |
|
| |
Torque Bias Input Selection | Direct Access Number — F342 | |
Program ⇒ Torque ⇒ Torque Control | Parameter Type — Selection List | |
Once enabled at parameter F341, this parameter sets the source of the input | Factory Default — Disabled | |
Changeable During Run — Yes | ||
signal that will set the torque level used for to provide the Braking Mode | ||
| ||
Selection function of parameter F341. |
|
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485
6 — RS485
7 — Communication Option Board
8 — RX2 Option (AI1)
Panel Torque Bias | Direct Access Number — F343 | |
Program ⇒ Torque ⇒ Torque Control | Parameter Type — Numerical | |
Once enabled at parameter F341, this parameter establishes the torque bias | Factory Default — 100.00 | |
Changeable During Run — Yes | ||
setting to which the setting of F342 will either add to or subtract from to | ||
| ||
produce the final torque value used to carry out the Braking Mode Selection | Minimum — | |
function of parameter F341. | Maximum — +250.00 | |
| ||
| Units — % |
Panel Torque Gain
Program ⇒ Torque ⇒ Torque Control
Once enabled at parameter F341, this parameter sets the sensitivity of the torque control source selected at F342 for the Braking Mode Selection function of parameter F341.
Direct Access Number — F344
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Release Time
Program ⇒ Torque ⇒ Torque Control
Once enabled at parameter F341, this parameter sets the time that the brake will hold after the requirements of the Braking Mode Selection function of parameter F341 have been met.
Direct Access Number — F345
Parameter Type — Numerical
Factory Default — 0.05
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Creeping Frequency
Program ⇒ Torque ⇒ Torque Control
Once enabled at parameter F341, and while running, upon receiving a Stop command this parameter sets an output frequency to be provided for the duration of the time setting of parameter F347.
Direct Access Number — F346
Parameter Type — Numerical
Factory Default — 3.00
Changeable During Run — Yes
Minimum — F240 Setting
Maximum — 20.0
Units — Hz
H9 ASD Installation and Operation Manual | 143 |