F706 | F706 |
Display Bias
Program ⇒ Utilities ⇒ Display Parameters
In conjunction with the setting of F702, this parameter sets the bias of the front panel speed display.
The frequency entered here will be multiplied by the setting of F702 and then displayed as the zero value on the front panel display.
Direct Access Number — F706
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Change Step Selection 1
Program ⇒ Utilities ⇒ Display Parameters
In conjunction with the parameter setting of F708, this parameter sets the amount that the output speed will increase or decrease for each speed command change entered from the front panel using the Rotary Encoder.
Direct Access Number — F707
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Change Step Selection 2
Program ⇒ Utilities ⇒ Display Parameters
The parameter is used to modify the degree that the setting of F707 affects the output speed changes that are input from the front panel using the Rotary Encoder.
Selecting a zero value here disables this parameter and the resulting
Selecting a
⋅ F708
Outpu tFrequ enc yDisplay ed = In te rna lly Command edFreque ncy
F707
Direct Access Number — F708
Parameter Type — Numerical
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Operation Command Clear Selection When ST Off
Program ⇒ Special ⇒ Operation Panel Parameters
Upon deactivation of the ST terminal while operating in the Local mode, the motor will halt — this parameter setting is used to allow for the reactivation of the motor without user intervention upon the reactivation of the ST terminal.
Upon reactivation of the ST terminal in this condition the ASD will resume the Run condition and the motor will start (1 — Retain Run Command).
This feature may be Disabled and the Run command must be
DANGER
WHEN ENABLED THE ASD WILL RESUME THE RUN CONDITION
WHEN THE ST TERMINAL IS REACTIVATED.
Settings:
0 — Clear Panel Run Command
1 — Retain Panel Run Command
Direct Access Number — F719 Parameter Type — Selection List Factory Default — Retain Panel Run
Command
Changeable During Run — Yes
200 | H9 ASD Installation and Operation Manual |