Toshiba H9 F220 F221, RX Input Point 1 Rate, RX Input Point 2 Rate, RX Input Torque Control Setup

Models: H9

1 289
Download 289 pages 12.38 Kb
Page 123
Image 123

F220

F221

RX Input Point 1 Rate

Program Torque Setpoints

This parameter is used to set the gain and bias of the RX input terminal when the RX terminal is used as the control input while operating in the Torque Control mode.

RX Input Torque Control Setup

Perform the following setup to allow the system to receive Torque Control input at the RX input terminal:

Program Fundamental Standard Mode Selection Frequency Mode

RX.

Program Fundamental Standard Mode Selection Command Mode Selection Terminal Block.

Torque Control

Perform the following setup to allow the system to perform Torque Control from the RX input terminal:

Set RX Input Point 1 Rate (F220).

Set RX Input Point 1 Setting (F216) — the input analog signal level that corresponds to the torque setting at RX Input Point 1 Rate.

Set RX Input Point 2 Rate (F221).

Set RX Input Point 2 Setting (F218) — the input analog signal level that corresponds to the speed setting at RX Input Point 2 Rate.

Provide a Run command (F and/or R).

Torque Control is accomplished by establishing an associated V/f output pattern for a given RX input level.

Once set, as the RX input voltage changes, the ASD output speed and/or torque will vary in accordance with the above settings.

This parameter sets RX Input Point 1 Rate and is the output torque value that is associated with the setting of RX Input Point 1 Setting when operating in the Torque Control mode.

This value is entered as -250% to +250% of the rated torque.

Direct Access Number — F220

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.00

Maximum — +250.00

Units — %

Torque Settings

RX Input Point 2 Rate

Program Torque Setpoints

This parameter is used to set the gain and bias of the RX input terminal when the RX terminal is used as the control input while operating in the Torque Control mode.

Torque Control is accomplished by establishing an associated V/f output pattern for a given RX input level.

This parameter sets RX Input Point 2 Rate and is the output torque value that is associated with the setting of RX Input Point 2 Setting when operating in the Torque Control mode.

This value is entered as -250% to +250% of the rated torque.

See RX Input Point 1 Rate for more information on this setting.

Direct Access Number — F221

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.00

Maximum — +250.00

Units — %

H9 ASD Installation and Operation Manual

115

Page 123
Image 123
Toshiba H9 operation manual F220 F221, RX Input Point 1 Rate, RX Input Point 2 Rate, RX Input Torque Control Setup