H9 ASD Installation and Operation Manual 235

Traverse Selection

Program Special Traverse
This parameter settin g is used in the setup of the Trav erse control mode of
operation and is used in conjunction with the discrete terminal activation of the
Traverse Permission Signal.
This parameter is use d to enable the Traverse function. The Travers e function
is activated via the discret e in put terminal (see Table 5 on pg. 236).
See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F980
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No

Traverse Acceleration Time

Program Special Traverse
This parameter settin g is used in the setup of the Trav erse control mode of
operation. This setting establishes the acceleration rate used during the
Traverse function.
See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.
Direct Access Number — F981
Parameter Type — Numeri cal
Factory Default — 25.0
Changeable During Run — No
Minimum — 0.1
Maximum — 120.0
Units — Seconds

Traverse Deceleration Time

Program Special Traverse
This parameter settin g is used in the setup of the Trav erse control mode of
operation. This setting establishes the deceleration rate used during the
Traverse function.
See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.
Direct Access Number — F982
Parameter Type — Numeri cal
Factory Default — 25.0
Changeable During Run — No
Minimum — 0.1
Maximum — 120.0
Units — Seconds

Traverse Step

Program Special Traverse
This parameter settin g is used in the setup of the Trav erse control mode of
operation. This setting is use d as a mu ltiplier to establish the amoun t that the
frequency is increased or decreased while using the Traverse function.
See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.
Direct Access Number — F983
Parameter Type — Numeri cal
Factory Default — 10.0
Changeable During Run — No
Minimum — 0.0
Maximum — 25.0
Units — %

Traverse Jump Step

Program Special Traverse
This parameter settin g is used in the setup of the Trav erse control mode of
operation. This setting is use d as a mu ltiplier to establish the amoun t that the
frequency is increased or decreased while using the Traverse function when a
short burst of rapid speed change is required.
See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.
Direct Access Number — F984
Parameter Type — Numeri cal
Factory Default — 10.0
Changeable During Run — No
Minimum — 0.0
Maximum — 50.0
Units — %