F980

 

F984

 

 

 

Traverse Selection

Direct Access Number —

F980

Program Special Traverse

Parameter Type — Selection List

This parameter setting is used in the setup of the Traverse control mode of

Factory Default — Disabled

 

Changeable During Run — No

operation and is used in conjunction with the discrete terminal activation of the

 

 

Traverse Permission Signal.

 

 

This parameter is used to enable the Traverse function. The Traverse function

 

 

is activated via the discrete input terminal (see Table 5 on pg. 236).

 

 

See the Traverse Control Instruction Manual (P/N 58693) for more

 

 

information on this feature.

 

 

Settings:

 

 

0 — Disabled

 

 

1 — Enabled

 

 

 

 

 

Traverse Acceleration Time

Direct Access Number —

F981

Program Special Traverse

Parameter Type — Numerical

This parameter setting is used in the setup of the Traverse control mode of

Factory Default — 25.0

 

Changeable During Run — No

operation. This setting establishes the acceleration rate used during the

 

 

Traverse function.

Minimum — 0.1

 

See the Traverse Control Instruction Manual (P/N 58693) for more

Maximum — 120.0

 

Units — Seconds

 

information on this feature.

 

 

 

 

 

 

Traverse Deceleration Time

Direct Access Number —

F982

Program Special Traverse

Parameter Type — Numerical

This parameter setting is used in the setup of the Traverse control mode of

Factory Default — 25.0

 

Changeable During Run — No

operation. This setting establishes the deceleration rate used during the

 

 

Traverse function.

Minimum — 0.1

 

See the Traverse Control Instruction Manual (P/N 58693) for more

Maximum — 120.0

 

Units — Seconds

 

information on this feature.

 

 

 

 

 

 

Traverse Step

Direct Access Number —

F983

Program Special Traverse

Parameter Type — Numerical

This parameter setting is used in the setup of the Traverse control mode of

Factory Default — 10.0

 

Changeable During Run — No

operation. This setting is used as a multiplier to establish the amount that the

 

 

frequency is increased or decreased while using the Traverse function.

Minimum — 0.0

 

See the Traverse Control Instruction Manual (P/N 58693) for more

Maximum — 25.0

 

Units — %

 

information on this feature.

 

 

 

 

 

 

Traverse Jump Step

Direct Access Number —

F984

Program Special Traverse

Parameter Type — Numerical

This parameter setting is used in the setup of the Traverse control mode of

Factory Default — 10.0

 

Changeable During Run — No

operation. This setting is used as a multiplier to establish the amount that the

 

 

frequency is increased or decreased while using the Traverse function when a

Minimum — 0.0

 

short burst of rapid speed change is required.

Maximum — 50.0

 

 

 

See the Traverse Control Instruction Manual (P/N 58693) for more

Units — %

 

information on this feature.

 

H9 ASD Installation and Operation Manual

235

Page 243
Image 243