F980 |
| F984 | |
|
|
| |
Traverse Selection | Direct Access Number — | F980 | |
Program ⇒ Special ⇒ Traverse | Parameter Type — Selection List | ||
This parameter setting is used in the setup of the Traverse control mode of | Factory Default — Disabled |
| |
Changeable During Run — No | |||
operation and is used in conjunction with the discrete terminal activation of the | |||
|
| ||
Traverse Permission Signal. |
|
| |
This parameter is used to enable the Traverse function. The Traverse function |
|
| |
is activated via the discrete input terminal (see Table 5 on pg. 236). |
|
| |
See the Traverse Control Instruction Manual (P/N 58693) for more |
|
| |
information on this feature. |
|
| |
Settings: |
|
| |
0 — Disabled |
|
| |
1 — Enabled |
|
| |
|
|
| |
Traverse Acceleration Time | Direct Access Number — | F981 | |
Program ⇒ Special ⇒ Traverse | Parameter Type — Numerical | ||
This parameter setting is used in the setup of the Traverse control mode of | Factory Default — 25.0 |
| |
Changeable During Run — No | |||
operation. This setting establishes the acceleration rate used during the | |||
|
| ||
Traverse function. | Minimum — 0.1 |
| |
See the Traverse Control Instruction Manual (P/N 58693) for more | Maximum — 120.0 |
| |
Units — Seconds |
| ||
information on this feature. |
| ||
|
| ||
|
|
| |
Traverse Deceleration Time | Direct Access Number — | F982 | |
Program ⇒ Special ⇒ Traverse | Parameter Type — Numerical | ||
This parameter setting is used in the setup of the Traverse control mode of | Factory Default — 25.0 |
| |
Changeable During Run — No | |||
operation. This setting establishes the deceleration rate used during the | |||
|
| ||
Traverse function. | Minimum — 0.1 |
| |
See the Traverse Control Instruction Manual (P/N 58693) for more | Maximum — 120.0 |
| |
Units — Seconds |
| ||
information on this feature. |
| ||
|
| ||
|
|
| |
Traverse Step | Direct Access Number — | F983 | |
Program ⇒ Special ⇒ Traverse | Parameter Type — Numerical | ||
This parameter setting is used in the setup of the Traverse control mode of | Factory Default — 10.0 |
| |
Changeable During Run — No | |||
operation. This setting is used as a multiplier to establish the amount that the | |||
|
| ||
frequency is increased or decreased while using the Traverse function. | Minimum — 0.0 |
| |
See the Traverse Control Instruction Manual (P/N 58693) for more | Maximum — 25.0 |
| |
Units — % |
| ||
information on this feature. |
| ||
|
| ||
|
|
| |
Traverse Jump Step | Direct Access Number — | F984 | |
Program ⇒ Special ⇒ Traverse | Parameter Type — Numerical | ||
This parameter setting is used in the setup of the Traverse control mode of | Factory Default — 10.0 |
| |
Changeable During Run — No | |||
operation. This setting is used as a multiplier to establish the amount that the | |||
|
| ||
frequency is increased or decreased while using the Traverse function when a | Minimum — 0.0 |
| |
short burst of rapid speed change is required. | Maximum — 50.0 |
| |
|
|
See the Traverse Control Instruction Manual (P/N 58693) for more | Units — % |
| |
information on this feature. |
|
H9 ASD Installation and Operation Manual | 235 |