Toshiba H9 operation manual RX2 AI1 Input Point 2 Rate, Direct Access Number F227

Models: H9

1 289
Download 289 pages 12.38 Kb
Page 127
Image 127

F227

F227

RX2 (AI1) Input Point 2 Rate

Program Torque Setpoints

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal when the RX2 (AI1) terminal is used as the control input while operating in the Torque Control mode.

Torque Control is accomplished by establishing an associated V/f output pattern for a given RX2 (AI1) input level.

This parameter sets RX2 (AI1) Input Point 2 Rate and is the output torque value that is associated with the setting of RX2 (AI1) Input Point 2 Setting when operating in the Torque Control mode.

This value is entered as -250% to +250% of the rated torque.

See RX2 (AI1) Input Point 1 Rate for more information on this setting.

Direct Access Number — F227

Parameter Type — Numerical

Factory Default — 100.00

Changeable During Run — Yes

Minimum — -250.00

Maximum — +250.00

Units — %

H9 ASD Installation and Operation Manual

119

Page 127
Image 127
Toshiba H9 operation manual RX2 AI1 Input Point 2 Rate, Direct Access Number F227