F683

 

F689

 

 

 

FM Bias Adjustment

Direct Access Number —

F683

Program Terminal Analog Output Terminals

Parameter Type — Numerical

This parameter setting is used to ensure that a zero-level input signal produces a

Factory Default — 0.0

 

Changeable During Run — Yes

zero-level output at the FM terminal.

 

 

Set the function of F005 to zero and then set this parameter to zero for proper

Minimum — -10.0

 

 

 

operation.

Maximum — +100.0

 

See F005 for more information on this setting.

Units — %

 

 

 

 

AM Output Gradient Characteristic

Direct Access Number —

F685

Program Terminal Analog Output Terminals

Parameter Type — Selection List

This parameter sets the output response polarity of the AM output terminal.

Factory Default — Plus

 

Changeable During Run — Yes

The AM output terminal response may be set to respond inversely (-) or

 

 

directly (+) to the input signal.

 

 

See F670 for more information on this setting.

 

 

Settings:

 

 

0 — Minus (Negative Gradient)

 

 

1 — Plus (Positive Gradient)

 

 

 

 

 

AM Bias Adjustment

Direct Access Number —

F686

Program Terminal Analog Output Terminals

Parameter Type — Numerical

This parameter setting is used to ensure that a zero-level input signal produces a

Factory Default — 0.0

 

Changeable During Run — Yes

zero-level output at the AM terminal.

 

 

Set the function set at F670 to zero and then set this parameter to zero for

Minimum — -10.0

 

 

 

proper operation.

Maximum — +100.0

 

See F670 for more information on this setting.

Units — %

 

 

 

 

MON 1 Voltage/Current Output Switching

Direct Access Number —

F688

Program Terminal Analog Output Terminals

Parameter Type — Selection List

This parameter is used to set the output signal type of the MON1 output

Factory Default — 0 – 10V

 

Changeable During Run — Yes

terminal.

 

 

Settings

 

 

0 — -10V – +10V

 

 

1 — 0 – 10V

 

 

2 — 0 – 20 mA

 

 

 

 

 

MON 1 Output Gradient Characteristic

Direct Access Number —

F689

Program Terminal Analog Output Terminals

Parameter Type — Selection List

 

Factory Default — Plus

 

This parameter sets the output response polarity of the MON1 output terminal.

The MON1 output terminal response may be set to respond inversely (-) or directly (+) to the input signal.

See parameter F672 for more information on this setting. Settings:

0 — Minus (Negative Gradient)

1 — Plus (Positive Gradient)

Changeable During Run — Yes

H9 ASD Installation and Operation Manual

197

Page 205
Image 205
Toshiba H9 operation manual F683 F689