Panel Stop Pattern
Program ⇒ Special ⇒ Operation Panel Parameters
While operating in the Local mode this parameter determines the method used to stop the motor when the stop command is issued via the EOI.
The Decel Stop setting enables the Dynamic Braking system that is setup at F304 or the DC Injection Braking system that is setup at F250, F251, and
F252.
The Coast Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Settings:
0 — Deceleration Stop
1 — Coast Stop
Direct Access Number — F721
Parameter Type — Selection List
Factory Default — Deceleration Stop
Changeable During Run — Yes
Note: The Stop Pattern setting has no effect on the Emergency Off
settings of F603. This parameter may also be accessed by pressing the ESC key from the Frequency Command screen.
Panel Torque Command | Direct Access Number — | F725 | |
Program ⇒ Special ⇒ Operation Panel Parameters | Parameter Type — Numerical | ||
While operating using the LED Keypad Option this parameter sets the torque | Factory Default — 0.00 |
| |
Changeable During Run — Yes | |||
command. | |||
|
| ||
| Minimum — |
| |
| Maximum — +250.00 |
| |
|
|
| |
Panel Tension Torque Bias | Direct Access Number — | F727 | |
Program ⇒ Special ⇒ Operation Panel Parameters | Parameter Type — Numerical | ||
While operating using the LED Keypad Option this parameter sets the Torque | Factory Default — 0.00 |
| |
Changeable During Run — Yes | |||
Bias. | |||
|
| ||
| Minimum — |
| |
| Maximum — +250.00 |
| |
| Units — % |
| |
|
|
| |
Panel Load Sharing Gain | Direct Access Number — | F728 | |
Program ⇒ Special ⇒ Operation Panel Parameters | Parameter Type — Numerical | ||
| Factory Default — 100.00 |
|
While operating using the LED Keypad Option this parameter is used to set
the Load Sharing Gain.
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Panel Override Multiplication Gain
Program ⇒ Special ⇒ Operation Panel Parameters
While operating using the LED Keypad Option this parameter provides a value to be used in the event that F729 (setting) is selected for the Frequency
Override Multiplying Input (F661).
Direct Access Number — F729
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum —
Maximum — 100.00
Units — %
H9 ASD Installation and Operation Manual | 201 |