Toshiba H9 operation manual F252 F256

Models: H9

1 289
Download 289 pages 12.38 Kb
Page 133
Image 133

F252

F256

 

 

DC Injection Braking Time

Direct Access Number — F252

Program Protection DC Braking

Parameter Type — Numerical

This parameter setting is used to set the on-time duration of the DC Injection

Factory Default — 1.0

Changeable During Run — Yes

Braking.

 

 

Minimum — 0.0

 

Maximum — 20.0

 

Units — Seconds

Forward/Reverse DC Injection Braking Priority

Program Protection DC Braking

This parameter setting determines if DC Injection braking is to be used during a change in the direction of the motor.

Settings:

0 — Disabled

1 — Enabled

Direct Access Number — F253

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Motor Shaft Fixing Control

Program Protection DC Braking

This parameter Enables/Disables a continuous DC injection at half of the amperage setting of F251 into a stopped motor. This feature is useful in preheating the motor or to keep the rotor from spinning freely.

Motor Shaft Stationary Control starts after the DC injection brake stops the motor and continues until ST CC is opened, power is turned off, an Emergency Off command is received, or this parameter is changed.

Enabling this feature will also require a non-zero entry at F250.

Settings:

0 — Disabled

1 — Enabled

Direct Access Number — F254

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

0 Hz Command Output

Direct Access Number — F255

Program Special Special Parameters

Parameter Type — Selection List

This parameter is used to set the go-to-zero method to be used by the ASD in

Factory Default — Standard (DC

Injection Braking)

the event that the ASD is commanded to go to zero Hz.

Changeable During Run — No

 

Settings:

 

0 — Standard (DC Injection Braking)

 

1 — 0 Hz Command

 

 

 

Time Limit For Lower-Limit Frequency Operation

Direct Access Number — F256

Program Fundamental Frequency Settings

Parameter Type — Numerical

This parameter sets the time that the ASD is allowed to operate below the

Factory Default — 0.0

Changeable During Run — Yes

Lower Limit setting before an alarm and subsequent fault is incurred.

 

 

Minimum — 0.0

 

Maximum — 600.0

 

Units — Seconds

H9 ASD Installation and Operation Manual

125

Page 133
Image 133
Toshiba H9 operation manual F252 F256