F616

F621

Overtorque Detection Level (Positive Torque)

Program Protection Overtorque Parameters

This parameter sets the torque threshold level that is used as a setpoint for overtorque tripping during positive torque. This setting is a percentage of the maximum rated torque of the drive.

This function is enabled at F615.

Direct Access Number — F616

Parameter Type — Numerical

Factory Default — 150.00

Changeable During Run — No

Minimum — 0.00

Maximum — 250.00

Units — %

Overtorque Detection Level (Negative Torque)

Program Protection Overtorque Parameters

This parameter sets the torque threshold level that is used as a setpoint for overtorque tripping during negative torque (regen). This setting is a percentage of the maximum rated torque of the drive.

This function is enabled at F615.

Direct Access Number — F617

Parameter Type — Numerical

Factory Default — 150.00

Changeable During Run — No

Minimum — 0.00

Maximum — 250.00

Units — %

Overtorque Detection Time

Program Protection Overtorque Parameters

This parameter sets the amount of time that the overtorque condition may exceed the tripping threshold level set at F616 and F617 before a trip occurs.

This function is enabled at F615.

Direct Access Number — F618

Parameter Type — Numerical

Factory Default — 0.50

Changeable During Run — No

Minimum — 0.00

Maximum — 10.0

Units — Seconds

Overtorque Detection Hysteresis

Program Protection Overtorque Parameters

During a momentary overtorque condition, this parameter provides a torque threshold level to which the overtorque condition must return within the time setting of F618 or an Overtorque Trip will be incurred.

Direct Access Number — F619

Parameter Type — Numerical

Factory Default — 10.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 100.00

Units — %

Cooling Fan Control

Direct Access Number —

F620

Program Protection Special Protection Parameters

Parameter Type — Selection List

This parameter sets the cooling fan run-time command.

Factory Default — Automatic

Changeable During Run — Yes

 

Settings:

 

 

0 — Automatic

 

 

1 — Always On

 

 

 

 

 

Cumulative Operation Time Alarm

Direct Access Number —

F621

Program Protection Special Protection Parameters

Parameter Type — Numerical

This parameter sets a run-time value that, once exceeded, closes a discrete

Factory Default — 610.0

 

Changeable During Run — Yes

output contact. The output signal may be used to control external equipment or

 

 

used to engage a brake.

Minimum — 0.0

 

Associate the Total-operation-hours Alarm setting of Table 8 on pg. 241 to a

Maximum — 999.9

 

discrete output contactor.

Units — Hours (X 10)

 

 

 

Note: The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).

186

H9 ASD Installation and Operation Manual

Page 194
Image 194
Toshiba H9 operation manual F616 F621