Overtorque Detection Level (Positive Torque)
Program ⇒ Protection ⇒ Overtorque Parameters
This parameter sets the torque threshold level that is used as a setpoint for overtorque tripping during positive torque. This setting is a percentage of the maximum rated torque of the drive.
This function is enabled at F615.
Direct Access Number — F616
Parameter Type — Numerical
Factory Default — 150.00
Changeable During Run — No
Minimum — 0.00
Maximum — 250.00
Units — %
Overtorque Detection Level (Negative Torque)
Program ⇒ Protection ⇒ Overtorque Parameters
This parameter sets the torque threshold level that is used as a setpoint for overtorque tripping during negative torque (regen). This setting is a percentage of the maximum rated torque of the drive.
This function is enabled at F615.
Direct Access Number — F617
Parameter Type — Numerical
Factory Default — 150.00
Changeable During Run — No
Minimum — 0.00
Maximum — 250.00
Units — %
Overtorque Detection Time
Program ⇒ Protection ⇒ Overtorque Parameters
This parameter sets the amount of time that the overtorque condition may exceed the tripping threshold level set at F616 and F617 before a trip occurs.
This function is enabled at F615.
Direct Access Number — F618
Parameter Type — Numerical
Factory Default — 0.50
Changeable During Run — No
Minimum — 0.00
Maximum — 10.0
Units — Seconds
Overtorque Detection Hysteresis
Program ⇒ Protection ⇒ Overtorque Parameters
During a momentary overtorque condition, this parameter provides a torque threshold level to which the overtorque condition must return within the time setting of F618 or an Overtorque Trip will be incurred.
Direct Access Number — F619
Parameter Type — Numerical
Factory Default — 10.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Cooling Fan Control | Direct Access Number — | F620 | |
Program ⇒ Protection ⇒ Special Protection Parameters | Parameter Type — Selection List | ||
This parameter sets the cooling fan | Factory Default — Automatic | ||
Changeable During Run — Yes | |||
| |||
Settings: |
|
| |
0 — Automatic |
|
| |
1 — Always On |
|
| |
|
|
| |
Cumulative Operation Time Alarm | Direct Access Number — | F621 | |
Program ⇒ Protection ⇒ Special Protection Parameters | Parameter Type — Numerical | ||
This parameter sets a | Factory Default — 610.0 |
| |
Changeable During Run — Yes | |||
output contact. The output signal may be used to control external equipment or | |||
|
| ||
used to engage a brake. | Minimum — 0.0 |
| |
Associate the | Maximum — 999.9 |
| |
discrete output contactor. | Units — Hours (X 10) |
| |
|
|
Note: The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
186 | H9 ASD Installation and Operation Manual |