F236

 

F241

 

 

 

PG Input Point 2 Setting

Direct Access Number —

F236

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

This parameter is used to set the direction and speed of the PG input terminals

Factory Default — 0

 

Changeable During Run — Yes

when the PG terminals are used as the control input.

 

 

This parameter sets the PG input signal that is associated with PG Point 2

Minimum — 0

 

 

 

Frequency.

Maximum — 100

 

This value is entered as 0% to 100% of the PG input signal range.

Units — %

 

See PG Point 1 Setting for further information on this setting.

 

 

 

 

 

PG Input Point 2 Frequency

Direct Access Number —

F237

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

This parameter is used to set the direction and speed of the PG input terminals

Factory Default — 60.00

 

Changeable During Run — Yes

when the PG terminal are used as the control input.

 

 

This parameter sets PG Point 2 Frequency and is the frequency that is

Minimum — 0.00

 

Maximum — Max. Freq. (F011)

associated with the setting of PG Point 2 Setting.

See PG Point 1 Setting for further information on this setting.

Units — Hz

 

 

 

 

Start Frequency

Direct Access Number —

F240

Program Special Frequency Control

Parameter Type — Numerical

The output of the drive will remain at 0.0 Hz until the programmed speed value

Factory Default — 0.10

 

Changeable During Run — Yes

exceeds this setting during startup. Once exceeded during startup, the output

 

 

frequency of the drive will accelerate to the programmed setting.

Minimum — 0.00

 

Output frequencies below the Start Frequency will not be output from the

Maximum — Max. Freq. (F011)

drive during startup. However, once reaching the Start Frequency, speed

Units — Hz

 

values below the Start Frequency may be output from the drive.

 

 

 

If the setting of this parameter results in an overcurrent condition at startup,

 

 

reduce the setting of this parameter to a value less than the rated slippage of the

 

 

motor.

 

 

If zero-speed torque is required, set this parameter and F243 to 0.0 Hz.

 

 

This setting will override the setting of F244 if this setting has a higher value.

 

 

This parameter setting is used during a Jog as the Lower Limit frequency (see

 

 

F260).

 

 

 

 

 

Run Frequency

Direct Access Number —

F241

Program Special Frequency Control

Parameter Type — Numerical

This parameter establishes a center frequency (Run Frequency) of a frequency

Factory Default — 0.00

 

Changeable During Run — Yes

band.

 

 

Parameter F242 provides a plus-or-minus value for the Run Frequency; thus,

Minimum — 0.00

 

Maximum — Max. Freq. (F011)

establishing a frequency band.

During acceleration, the drive will not output a signal to the motor until the

Units — Hz

 

lower level of the band is reached.

 

 

During deceleration, the drive will continue to output the programmed deceleration signal to the motor until the lower level of the band is reached; at which time the output will go to 0.0 Hz.

H9 ASD Installation and Operation Manual

123

Page 131
Image 131