F236 |
| F241 | |
|
|
| |
PG Input Point 2 Setting | Direct Access Number — | F236 | |
Program ⇒ Frequency ⇒ Speed Reference Setpoints | Parameter Type — Numerical | ||
This parameter is used to set the direction and speed of the PG input terminals | Factory Default — 0 |
| |
Changeable During Run — Yes | |||
when the PG terminals are used as the control input. | |||
|
| ||
This parameter sets the PG input signal that is associated with PG Point 2 | Minimum — 0 |
| |
|
| ||
Frequency. | Maximum — 100 |
| |
This value is entered as 0% to 100% of the PG input signal range. | Units — % |
| |
See PG Point 1 Setting for further information on this setting. |
|
| |
|
|
| |
PG Input Point 2 Frequency | Direct Access Number — | F237 | |
Program ⇒ Frequency ⇒ Speed Reference Setpoints | Parameter Type — Numerical | ||
This parameter is used to set the direction and speed of the PG input terminals | Factory Default — 60.00 |
| |
Changeable During Run — Yes | |||
when the PG terminal are used as the control input. | |||
|
| ||
This parameter sets PG Point 2 Frequency and is the frequency that is | Minimum — 0.00 |
| |
Maximum — Max. Freq. (F011) | |||
associated with the setting of PG Point 2 Setting. | |||
See PG Point 1 Setting for further information on this setting. | Units — Hz |
| |
|
|
| |
Start Frequency | Direct Access Number — | F240 | |
Program ⇒ Special ⇒ Frequency Control | Parameter Type — Numerical | ||
The output of the drive will remain at 0.0 Hz until the programmed speed value | Factory Default — 0.10 |
| |
Changeable During Run — Yes | |||
exceeds this setting during startup. Once exceeded during startup, the output | |||
|
| ||
frequency of the drive will accelerate to the programmed setting. | Minimum — 0.00 |
| |
Output frequencies below the Start Frequency will not be output from the | Maximum — Max. Freq. (F011) | ||
drive during startup. However, once reaching the Start Frequency, speed | Units — Hz |
| |
values below the Start Frequency may be output from the drive. |
| ||
|
| ||
If the setting of this parameter results in an overcurrent condition at startup, |
|
| |
reduce the setting of this parameter to a value less than the rated slippage of the |
|
| |
motor. |
|
| |
If |
|
| |
This setting will override the setting of F244 if this setting has a higher value. |
|
| |
This parameter setting is used during a Jog as the Lower Limit frequency (see |
|
| |
F260). |
|
| |
|
|
| |
Run Frequency | Direct Access Number — | F241 | |
Program ⇒ Special ⇒ Frequency Control | Parameter Type — Numerical | ||
This parameter establishes a center frequency (Run Frequency) of a frequency | Factory Default — 0.00 |
| |
Changeable During Run — Yes | |||
band. | |||
|
| ||
Parameter F242 provides a | Minimum — 0.00 |
| |
Maximum — Max. Freq. (F011) | |||
establishing a frequency band. | |||
During acceleration, the drive will not output a signal to the motor until the | Units — Hz |
| |
lower level of the band is reached. |
|
|
During deceleration, the drive will continue to output the programmed deceleration signal to the motor until the lower level of the band is reached; at which time the output will go to 0.0 Hz.
H9 ASD Installation and Operation Manual | 123 |