F294

F301

 

 

Preset Speed 15

Direct Access Number — F294

Program Frequency Preset Speeds

Parameter Type — Numerical

This parameter assigns an output frequency to binary number 1111 and is

Factory Default — 0.00

Changeable During Run — Yes

identified as Preset Speed #15. The binary number is applied to S1 S4 of the

Minimum — Lower Limit (F013)

Terminal Board to output the Preset Speed (see F018 for more information on

this parameter).

Maximum — Upper Limit (F012)

 

 

Units — Hz

 

 

PWM Carrier Frequency

Direct Access Number — F300

Program Special Carrier Frequency

Parameter Type — Numerical

This parameter sets the frequency of the pulse width modulation signal applied

Factory Default — 2.200

Changeable During Run — No

to the motor.

 

Note: When operating in the Vector Control mode the carrier

Minimum — 1.0

Maximum — (ASD-dependent)

frequency should be set to 2.2 kHz or above.

Units — kHz

 

Note: If the PWM carrier frequency is set at 2.0 kHz or above, it cannot be decreased below 2.0 kHz while running. If the PWM carrier frequency is set at 1.9 kHz or below, it cannot be increased above

2.0kHz while running. Either change requires that the ASD be stopped and restarted for the changes to take effect.

Auto Restart Selection

Program Protection Retry/Restart

This parameter Enables/Disables the ability of the drive to start into a spinning motor when the ST CC connection opens momentarily and is then closed (Break/Make ST) or after a power interruption (momentary power failure).

Settings:

0 — Off

1 — Enabled (at Power Failure)

2 — Enabled (at Make-Break ST-CC)

3 — Enabled (at Make-Break ST-CC or Power Failure) 4 — Enabled (at Run)

Direct Access Number — F301

Parameter Type — Selection List

Factory Default — Off

Changeable During Run — No

H9 ASD Installation and Operation Manual

133