F018

F019

eset Speed 1

Preset Speed 1

Program Frequency Preset Speeds

Up to 15 output frequency values that fall within the Lower Limit and the Upper Limit range may be programmed into the drive and output as a Preset Speed. This parameter assigns an output frequency to binary number 0001 and is identified as Preset Speed #1. The binary number is applied to S1 S4 of the Terminal Board to output the Preset Speed.

Perform the following setup to allow the system to receive Preset Speed control input at the S1 – S4 terminals:

Direct Access Number — F018

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — Lower Limit (F013)

Maximum — Upper Limit (F012)

Units — Hz

eset Speed 2

1. Program Fundamental Standard Mode Selection Command Mode

 

Preset Speed Truth Table

 

Terminal Block.

 

 

 

 

 

 

 

 

 

Preset

S4

S3

S2

S1

Output

 

2. Program Terminal Input Terminals S1 (set to Preset Speed

MSB

LSB

 

 

Command 1; LSB of 4-bit count). Repeat for S2 S4 (MSB of 4-bit count)

1

 

0

0

0

1

F018

 

 

as Preset Speed Command 2 4, respectively (all Normally Open).

 

 

 

 

 

 

 

 

 

 

 

 

2

 

0

0

1

0

F019

 

3.

Program Frequency Preset Speeds Preset Speed 1 (set an output

 

 

 

 

 

 

 

 

 

 

3

 

0

0

1

1

F020

 

 

frequency as Preset Speed #1; repeat for Preset Speeds 2 15 as

 

 

 

 

 

 

 

 

 

 

 

 

required).

 

 

 

 

 

 

 

 

 

4

 

0

1

0

0

F021

 

4. Program Pattern Run Operation Mode Preset Speed Operation

 

 

 

 

 

 

 

 

5

 

0

1

0

1

F022

 

 

Mode.

 

 

 

 

 

 

 

 

 

6

 

0

1

1

0

F023

 

 

 

 

 

 

Select Enabled to use the direction, accel/decel, and torque settings of the

 

 

 

 

 

 

 

 

 

7

 

0

1

1

1

F024

 

 

Preset Speed being run. The torque settings used will be as defined in F170

 

 

 

 

 

 

 

 

 

 

 

 

F181 and as selected via the associated discrete input terminals V/f

8

 

1

0

0

0

F287

 

 

Switching 1 and 2 in Table 5 on pg. 236.

 

 

 

 

 

 

 

 

 

9

 

1

0

0

1

F288

 

 

 

 

 

 

Select Disabled to use the speed setting only of the Preset Speed being run.

 

 

 

 

 

 

 

 

 

10

 

1

0

1

0

F289

 

 

 

 

 

5.

Place the system in the Remote mode (LocalRemote LED Off).

 

 

 

 

 

 

 

 

11

 

1

0

1

1

F290

 

 

 

 

 

6. Provide a Run command (connect F and/or R to CC).

 

 

 

 

 

 

 

 

12

 

1

1

0

0

F291

 

 

 

 

 

Connect S1 to CC to run Preset Speed #1 (S1 to CC = 0001 binary).

 

 

 

 

 

 

 

 

13

 

1

1

0

1

F292

 

With S1 S4 configured to output Preset Speeds (F115 F118), 0001 – 1111

 

 

 

 

 

 

 

 

14

 

1

1

1

0

F293

 

may be applied to S1 – S4 of the Terminal Board to run the associated Preset

 

 

 

 

 

 

 

 

 

 

Speed. If bidirectional operation is required, F and R must be connected to CC,

15

 

1

1

1

1

F294

 

and Preset Speed Operation Mode must be set to Enabled at F560.

 

 

 

 

 

 

 

 

Note: 1 = Terminal connected to CC.

 

With S1 being the least significant bit of a binary count, the S1 – S4 settings

 

 

 

 

 

 

 

 

 

will produce the programmed speed settings as indicated in the Preset Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Truth Table to the right.

 

 

 

 

 

 

 

 

Preset Speeds are also used in the Pattern Run mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Preset Speed 2

Direct Access Number — F019

Program Frequency Preset Speeds

Parameter Type — Numerical

 

 

This parameter assigns an output frequency to binary number 0010 and is

Factory Default — 0.0

 

 

 

Changeable During Run — Yes

 

 

identified as Preset Speed #2. The binary number is applied to S1 S4 of the

 

 

Minimum — Lower Limit (F013)

Terminal Board to output the Preset Speed (see F018 for more information on

this parameter).

Maximum — Upper Limit (F012)

 

 

Units — Hz

H9 ASD Installation and Operation Manual

83

Page 91
Image 91
Toshiba H9 operation manual F018 F019, Preset Speed Truth Table, Preset Output