LED

LCD

Description

 

Possible Causes

Display

Display

 

 

 

 

 

 

 

 

 

OC

Over Current

 

Defective IGBT (U, V, or W).

 

 

ASD output current greater than

• ASD output to the motor is connected incorrectly.

 

 

F601 setting.

 

 

 

Disconnect the motor and retry.

 

 

 

 

 

 

 

• ASD output phase-to-phase short.

 

 

 

• The ASD is starting into a spinning motor.

 

 

 

Motor/machine jammed.

 

 

 

• Mechanical brake engaged while the ASD is starting or

 

 

 

 

while running.

 

 

 

• Accel/Decel time is too short.

 

 

 

• Voltage Boost setting is too high.

 

 

 

Load fluctuations.

 

 

 

• ASD operating at an elevated temperature.

 

 

 

 

 

*OH

Overheat

 

ASD is operating at an elevated temperature.

 

 

ASD ambient temperature

• ASD is too close to heat-generating equipment.

 

 

excessive.

 

 

 

 

 

 

 

• Cooling fan vent is obstructed (see Mounting the H9

 

 

 

 

ASD on pg. 15).

 

 

 

• Cooling fan is inoperative.

 

 

 

• Internal thermistor is disconnected.

 

 

 

 

 

OJ

Timer

Run-time counter exceeded.

Type Reset required; select Clear run timer.

 

 

 

 

 

*OLI

ASD Overload

 

The carrier frequency is too high.

 

 

Load requirement in excess of

An excessive load.

 

 

the capability of the ASD.

 

 

 

 

 

 

 

• Acceleration time is too short.

 

 

 

• DC damping rate is set too high.

 

 

 

• The motor is starting into a spinning load after a

 

 

 

 

momentary power failure.

 

 

 

• The ASD is improperly matched to the application.

 

 

 

 

 

OLM

Motor Overload

 

V/f parameter improperly set.

 

 

Load requirement in excess of

Motor is locked.

 

 

the capability of the motor.

 

 

 

 

 

 

 

• Continuous operation at low speed.

 

 

 

• The load is in excess of what the motor can deliver.

 

 

 

 

 

*OLR

Resistor

Excessive current at the

Deceleration time is too short.

 

Overload

Dynamic Braking Resistor.

DBR configuration improperly set.

 

 

 

 

 

248

H9 ASD Installation and Operation Manual

Page 256
Image 256