F813

 

F825

 

 

 

Point 2 Setting

Direct Access Number —

F813

Program Communications Communication Reference Adjust

Parameter Type — Numerical

This parameter is used to set the gain and bias of the Communications

Factory Default — 100

 

Changeable During Run — Yes

Reference speed control input.

 

 

See F811 for more information on this setting.

Minimum — 0

 

 

 

This parameter sets the Communications Reference input value that represents

Maximum — 100

 

Units — %

 

Communications Reference Speed Setpoint #2 (frequency). This value is

 

entered as 0 to 100% of the Communications Reference input value range.

 

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

 

 

 

Point 2 Frequency

Direct Access Number —

F814

Program Communications Communication Reference Adjust

Parameter Type — Numerical

This parameter is used to set the gain and bias of the Communications

Factory Default — 60.00

 

Changeable During Run — Yes

Reference speed control input.

 

 

See F811 for more information on this setting.

Minimum — 0.00

 

Maximum — Max. Freq. (F011)

This parameter sets the Communications Reference Speed Setpoint #2.

 

 

Changes made to this parameter require that the power be cycled (Off then On)

Units — Hz

 

 

 

for the changes to take effect.

 

 

 

 

 

Baud Rate (RS485 4-wire)

Direct Access Number —

F820

Program Communications Communication Settings

Parameter Type — Selection List

This parameter sets the RSRS485 baud rate.

Factory Default — 19200

 

Changeable During Run — Yes

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

Settings:

 

 

0 — 9600 bps

 

 

1 — 19200 bps

 

 

2 — 38400 bps

 

 

 

 

 

RS485 Send Wait Time (RS485 4-wire)

Direct Access Number —

F825

Program Communications Communication Settings

Parameter Type — Numerical

This parameter sets the RS485 response delay time.

Factory Default — 0.00

 

Changeable During Run — Yes

 

Changes made to this parameter require that the power be cycled (Off then On)

Minimum — 0.00

 

for the changes to take effect.

Maximum — 2.00

 

 

 

Units — Seconds

208

H9 ASD Installation and Operation Manual

Page 216
Image 216
Toshiba H9 F813 F825, Point 2 Setting, Point 2 Frequency, Baud Rate RS485 4-wire, RS485 Send Wait Time RS485 4-wire