F813 |
| F825 | |
|
|
| |
Point 2 Setting | Direct Access Number — | F813 | |
Program ⇒ Communications ⇒ Communication Reference Adjust | Parameter Type — Numerical | ||
This parameter is used to set the gain and bias of the Communications | Factory Default — 100 |
| |
Changeable During Run — Yes | |||
Reference speed control input. | |||
|
| ||
See F811 for more information on this setting. | Minimum — 0 |
| |
|
| ||
This parameter sets the Communications Reference input value that represents | Maximum — 100 |
| |
Units — % |
| ||
Communications Reference Speed Setpoint #2 (frequency). This value is |
| ||
entered as 0 to 100% of the Communications Reference input value range. |
|
| |
Changes made to this parameter require that the power be cycled (Off then On) |
|
| |
for the changes to take effect. |
|
| |
|
|
| |
Point 2 Frequency | Direct Access Number — | F814 | |
Program ⇒ Communications ⇒ Communication Reference Adjust | Parameter Type — Numerical | ||
This parameter is used to set the gain and bias of the Communications | Factory Default — 60.00 |
| |
Changeable During Run — Yes | |||
Reference speed control input. | |||
|
| ||
See F811 for more information on this setting. | Minimum — 0.00 |
| |
Maximum — Max. Freq. (F011) | |||
This parameter sets the Communications Reference Speed Setpoint #2. | |||
|
| ||
Changes made to this parameter require that the power be cycled (Off then On) | Units — Hz |
| |
|
| ||
for the changes to take effect. |
|
| |
|
|
| |
Baud Rate (RS485 | Direct Access Number — | F820 | |
Program ⇒ Communications ⇒ Communication Settings | Parameter Type — Selection List | ||
This parameter sets the RSRS485 baud rate. | Factory Default — 19200 |
| |
Changeable During Run — Yes | |||
| |||
Changes made to this parameter require that the power be cycled (Off then On) |
|
| |
for the changes to take effect. |
|
| |
Settings: |
|
| |
0 — 9600 bps |
|
| |
1 — 19200 bps |
|
| |
2 — 38400 bps |
|
| |
|
|
| |
RS485 Send Wait Time (RS485 | Direct Access Number — | F825 | |
Program ⇒ Communications ⇒ Communication Settings | Parameter Type — Numerical | ||
This parameter sets the RS485 response delay time. | Factory Default — 0.00 |
| |
Changeable During Run — Yes | |||
| |||
Changes made to this parameter require that the power be cycled (Off then On) | Minimum — 0.00 |
| |
for the changes to take effect. | Maximum — 2.00 |
| |
|
|
Units — Seconds
208 | H9 ASD Installation and Operation Manual |