208 H9 ASD Installation and Operation Manual

Point 2 Setting

Program Communications Communication Reference Adjust
This parameter is use d to set the gain and bi as of the Communications
Reference speed control input.
See F811 for more information on this setting.
This parameter sets the Communications Reference input value that represents
Communications Reference Speed Setpoint #2 (frequency). This value is
entered as 0 to 100% of the Communications Reference input value range.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F813
Parameter Type — Numeri cal
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %

Point 2 Frequency

Program Communications Communication Reference Adjust
This parameter is use d to set the gain and bi as of the Communications
Reference speed control input.
See F811 for more information on this setting.
This parameter sets th e Communications Reference Speed Setpoint #2.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F814
Parameter Type — Numeri cal
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz

Baud Rate (RS485 4-wire)

Program Communications Communication Settings
This parameter sets th e RSRS485 baud rate.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
Direct Access Number — F820
Parameter Type — Selection List
Factory Default — 19200
Changeable During Run — Yes

RS485 Send Wait Time (RS485 4-wire)

Program Communications Communication Settings
This parameter sets th e RS485 response delay time.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F825
Parameter Type — Numeri cal
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds