F498

F501

Permanent Magnet (PM) Motor Constant 1

Program Motor PM Motor

This parameter is used with synchronous motor applications only.

Contact Toshiba Customer Service Department for information on this parameter.

Direct Access Number — F498

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — %

Permanent Magnet (PM) Motor Constant 2

Program Motor PM Motor

This parameter is used with synchronous motor applications only.

Contact Toshiba Customer Service Department for information on this parameter.

Direct Access Number — F499

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — %

Acceleration Time 2

Program Special Acc/Dec #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go from 0.0 Hz to the Maximum Frequency for the #2 Acceleration profile. The Accel/Decel pattern may be set using F502. The minimum Accel/Decel time may be set using F508.

This setting is also used to determine the acceleration rate of the UP/DOWN Frequency Functions.

Direct Access Number — F500

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000.0

Units — Seconds

Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads. Automatic Accel/Decel, Stall, and Ridethrough settings may lengthen the acceleration times.

Deceleration Time 2

Program Fundamental Accel/Decel #1 Settings

This parameter specifies the time in seconds for the output of the ASD to go from the Maximum Frequency to 0.0 Hz for the #2 Deceleration profile. The Accel/Decel pattern may be set using F502. The minimum Accel/Decel time may be set using F508.

This setting is also used to determine the deceleration rate of the UP/DOWN Frequency Functions.

Direct Access Number — F501

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads. Automatic Accel/Decel, Stall, and Ridethrough settings may lengthen the deceleration times.

164

H9 ASD Installation and Operation Manual

Page 172