Permanent Magnet (PM) Motor Constant 1
Program ⇒ Motor ⇒ PM Motor
This parameter is used with synchronous motor applications only.
Contact Toshiba Customer Service Department for information on this parameter.
Direct Access Number — F498
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Permanent Magnet (PM) Motor Constant 2
Program ⇒ Motor ⇒ PM Motor
This parameter is used with synchronous motor applications only.
Contact Toshiba Customer Service Department for information on this parameter.
Direct Access Number — F499
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Acceleration Time 2
Program ⇒ Special ⇒ Acc/Dec #1 – #4 Settings
This parameter specifies the time in seconds for the output of the ASD to go from 0.0 Hz to the Maximum Frequency for the #2 Acceleration profile. The Accel/Decel pattern may be set using F502. The minimum Accel/Decel time may be set using F508.
This setting is also used to determine the acceleration rate of the UP/DOWN Frequency Functions.
Direct Access Number — F500
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads. Automatic Accel/Decel, Stall, and Ridethrough settings may lengthen the acceleration times.
Deceleration Time 2
Program ⇒ Fundamental ⇒ Accel/Decel #1 Settings
This parameter specifies the time in seconds for the output of the ASD to go from the Maximum Frequency to 0.0 Hz for the #2 Deceleration profile. The Accel/Decel pattern may be set using F502. The minimum Accel/Decel time may be set using F508.
This setting is also used to determine the deceleration rate of the UP/DOWN Frequency Functions.
Direct Access Number — F501
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads. Automatic Accel/Decel, Stall, and Ridethrough settings may lengthen the deceleration times.
164 | H9 ASD Installation and Operation Manual |