Page 153
Image 153

F350

 

F353

 

 

 

 

Acceleration Suspend Frequency

Direct Access Number —

F350

Program Fundamental Accel/Decel #1 Settings

Parameter Type — Numerical

When Enabled at F349, this parameter is used to set the frequency at which the

Factory Default — 0.00

 

 

Changeable During Run — Yes

Acceleration Suspend function will activate.

 

 

 

During acceleration, this parameter sets the frequency at which acceleration

Minimum — 0.00

 

 

Maximum — Max. Freq. (F011)

will stop and the motor will run at the setting of this parameter for the time

setting of F351.

Units — Hz

 

 

 

 

 

 

 

 

 

Acceleration Suspend Time

Direct Access Number —

F351

Program Fundamental Accel/Decel #1 Settings

Parameter Type — Numerical

When Enabled at F349, this parameter is used to set the duration of activation

Factory Default — 0.0

 

 

Changeable During Run — Yes

of the Acceleration Suspend function when initiated by reaching the

 

 

 

Acceleration Suspend Frequency setting (F350).

Minimum — 0.0

 

 

Once this parameter times out the acceleration rate will resume from the point

Maximum — 10.0

 

 

of suspension.

Units — Seconds

 

 

 

 

 

 

 

 

 

Deceleration Suspend Frequency

Direct Access Number —

F352

Program Fundamental Accel/Decel #1 Settings

Parameter Type — Numerical

When Enabled at F349, this parameter is used to set the frequency at which the

Factory Default — 0.00

 

 

Changeable During Run — Yes

Deceleration Suspend function will activate.

 

 

 

During deceleration, this parameter sets the frequency at which deceleration

Minimum — 0.00

 

 

Maximum — Max. Freq. (F011)

will stop and the motor will run at the setting of this parameter for the time

setting of F353.

Units — Hz

 

 

 

 

 

 

 

 

 

Deceleration Suspend Time

Direct Access Number —

F353

Program Fundamental Accel/Decel #1 Settings

Parameter Type — Numerical

When Enabled at F349, this parameter is used to set the duration of activation

Factory Default — 0.0

 

 

Changeable During Run — Yes

of the Deceleration Suspend function when initiated by reaching the

 

 

 

Deceleration Suspend Frequency setting (F352).

Minimum — 0.0

 

 

Once this parameter times out the deceleration rate will resume from the point

Maximum — 10.0

 

 

of suspension.

Units — Seconds

 

 

 

 

 

H9 ASD Installation and Operation Manual

145

Page 153
Image 153