F223

 

F225

 

 

 

 

 

RX2 (AI1) Input Point 1 Frequency

Direct Access Number —

F223

 

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

 

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal

Factory Default — 0.00

 

 

Changeable During Run — Yes

 

when the RX2 (AI1) terminal is used as the control input while operating in the

 

 

 

 

Speed Control mode.

Minimum — 0.00

 

 

This parameter sets RX2 (AI1) Input Point 1 Frequency and is the frequency

Maximum — Max. Freq. (F011)

 

that is associated with the setting of RX2 (AI1) Input Point 1 Setting when

Units — Hz

 

 

operating in the Speed Control mode.

 

 

 

 

 

See RX2 (AI1) Input Point 1 Setting for more information on this setting.

 

 

 

 

 

 

 

RX2 (AI1) Input Point 2 Setting

Direct Access Number —

F224

 

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

 

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal

Factory Default — +100

 

 

Changeable During Run — Yes

 

when the RX2 (AI1) terminal is used as the control input while operating in the

 

 

 

 

Speed Control mode or the Torque Control mode.

Minimum — -100

 

 

This parameter sets the RX2 (AI1) input level that is associated with RX2

Maximum — +100

 

 

(AI1) Input Point 2 Frequency when operating in the Speed control mode or

Units — %

 

 

is associated with the RX2 (AI1) Input Point 2 Rate when operating in the

 

 

 

 

 

Torque Control mode.

 

 

 

This value is entered as -100% to +100% of the RX2 (AI1) input signal range.

 

 

 

See RX2 (AI1) Input Point 1 Setting for more information on this setting

 

 

 

when used for Speed control.

 

 

 

See RX2 (AI1) Input Point 1 Rate for more information on this setting when

 

 

 

used for Torque Control.

 

 

 

 

 

 

 

RX2 (AI1) Input Point 2 Frequency

Direct Access Number —

F225

 

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

 

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal

Factory Default — 60.00

 

 

Changeable During Run — Yes

 

when the RX2 (AI1) terminal is used as the control input while operating in the

 

 

 

 

Speed Control mode.

Minimum — 0.00

 

 

This parameter sets RX2 (AI1) Input Point 2 Frequency and is the frequency

Maximum — Max. Freq. (F011)

 

that is associated with the setting of RX2 (AI1) Input Point 2 Setting when

Units — Hz

 

 

 

 

operating in the Speed Control mode.

See RX2 (AI1) Input Point 1 Setting for more information on this setting.

H9 ASD Installation and Operation Manual

117

Page 125
Image 125