F926

F930

My Function Frequency Data 4

Program My Function My Function Data

This parameter is used to set the trigger threshold level of the analog signal of the My Function Frequency Data 4.

The analog signal is selected using the Input Setting number from Table 8 on pg. 241.

Direct Access Number — F926

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 200.00

Units — %

My Function Frequency Data 5

Program My Function My Function Data

This parameter is used to set the trigger threshold level of the analog signal of the My Function Frequency Data 5.

The analog signal is selected using the Input Setting number from Table 8 on pg. 241.

Direct Access Number — F927

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 200.00

Units — %

My Function Time Data 1

Program My Function My Function Data

This parameter is used to set the response delay of the My Function Time Data 1 terminal.

The applied discrete input signal must be present at the input terminal of the H9 ASD for the time setting here for a system response.

Discrete terminal input activation that does not equal or exceed this setting will be ignored.

Direct Access Number — F928

Parameter Type — Numerical

Factory Default — 0.01

Changeable During Run — Yes

Minimum — 0.01

Maximum — 600.00

Units — Seconds

My Function Time Data 2

Program My Function My Function Data

This parameter is used to set the response delay of the My Function Time Data 2 terminal.

The applied discrete input signal must be present at the input terminal of the H9 ASD for the time setting here for a system response.

Discrete terminal input activation that does not equal or exceed this setting will be ignored.

Direct Access Number — F929

Parameter Type — Numerical

Factory Default — 0.01

Changeable During Run — Yes

Minimum — 0.01

Maximum — 600.00

Units — Seconds

My Function Time Data 3

Program My Function My Function Data

This parameter is used to set the response delay of the My Function Time Data 3 terminal.

The applied discrete input signal must be present at the input terminal of the H9 ASD for the time setting here for a system response.

Discrete terminal input activation that does not equal or exceed this setting will be ignored.

Direct Access Number — F930

Parameter Type — Numerical

Factory Default — 0.01

Changeable During Run — Yes

Minimum — 0.01

Maximum — 600.00

Units — Seconds

H9 ASD Installation and Operation Manual

221

Page 229
Image 229
Toshiba H9 operation manual F926 F930, My Function Time Data