Toshiba H9 operation manual F007 F008, Forward/Reverse Run Selection, Program ⇒ Utilities

Models: H9

1 289
Download 289 pages 12.38 Kb
Page 87
Image 87

F007

F008

Reset

Type Reset

 

Program Utilities

 

This feature assists the user when performing fault analysis or by allowing a

 

quick system setup change when required. Performing a Type Reset results in

 

one of the following user-selected post-reset configurations.

 

Settings:

 

0

— None

 

1

— 50 Hz Setting

 

2

— 60 Hz Setting

 

3

— Reset to Factory Settings

 

4

— Clear Past Trips

 

5

— Clear Run Timer

 

6

— Initialize Typeform

 

7

— Save User Settings

 

8

— Restore User Settings

 

9

— Clear Cumulative Fan Timer

 

10

— Accel/Decel Time Setting 0.01 – 600.0 Seconds

 

11 — Accel/Decel Time Setting 0.1 – 6000.0 Seconds

 

12

— Update EOI Firmware

 

13

— Set EOI Memory to Default

 

14

— Save User Settings to EOI

 

15

— Restore User Settings from EOI

Direct Access Number — F007

Parameter Type — Selection List

Factory Default — None

Changeable During Run — No

Forward/Reverse Run Selection

Program Fundamental Standard Mode Selection

While operating using the keypad (F003 is set to EOI Keypad) this parameter sets the direction of motor rotation. This setting may be changed during operation. This setting will not override parameter F311 (Forward/Reverse Disable).

If either direction is disabled via parameter F311, the disabled direction will not be recognized if commanded by the keypad. If both directions are disabled via parameter F311, the direction command from the keypad will determine the direction of the motor rotation.

Settings:

0 — Forward

1 — Reverse

2— Forward (EOI-switchable F/R)

3— Reverse (EOI-switchable F/R)

Direct Access Number — F008

Parameter Type — Selection List

Factory Default — Forward

Changeable During Run — Yes

H9 ASD Installation and Operation Manual

79

Page 87
Image 87
Toshiba H9 operation manual F007 F008, Forward/Reverse Run Selection, Program ⇒ Utilities, Direct Access Number F007