Reset | Type Reset | ||
| Program ⇒ Utilities | ||
| This feature assists the user when performing fault analysis or by allowing a | ||
| quick system setup change when required. Performing a Type Reset results in | ||
| one of the following | ||
| Settings: | ||
| 0 | — None | |
| 1 | — 50 Hz Setting | |
| 2 | — 60 Hz Setting | |
| 3 | — Reset to Factory Settings | |
| 4 | — Clear Past Trips | |
| 5 | — Clear Run Timer | |
| 6 | — Initialize Typeform | |
| 7 | — Save User Settings | |
| 8 | — Restore User Settings | |
| 9 | — Clear Cumulative Fan Timer | |
| 10 | — Accel/Decel Time Setting 0.01 – 600.0 Seconds | |
| 11 — Accel/Decel Time Setting 0.1 – 6000.0 Seconds | ||
| 12 | — Update EOI Firmware | |
| 13 | — Set EOI Memory to Default | |
| 14 | — Save User Settings to EOI | |
| 15 | — Restore User Settings from EOI |
Direct Access Number — F007
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
Forward/Reverse Run Selection
Program ⇒ Fundamental ⇒ Standard Mode Selection
While operating using the keypad (F003 is set to EOI Keypad) this parameter sets the direction of motor rotation. This setting may be changed during operation. This setting will not override parameter F311 (Forward/Reverse Disable).
If either direction is disabled via parameter F311, the disabled direction will not be recognized if commanded by the keypad. If both directions are disabled via parameter F311, the direction command from the keypad will determine the direction of the motor rotation.
Settings:
0 — Forward
1 — Reverse
2— Forward
3— Reverse
Direct Access Number — F008
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — Yes
H9 ASD Installation and Operation Manual | 79 |