Display Units for Voltage and Current

Direct Access Number —

F701

Program Utilities Display Parameters

Parameter Type — Selection List

This parameter sets the unit of measurement for current and voltage values

Factory Default — %

 

Changeable During Run — Yes

displayed on the EOI.

 

 

Settings:

 

 

0 — %

 

 

1 — A/V

 

 

 

 

 

Display Unit Multiplication Factor

Direct Access Number —

F702

Program Utilities Display Parameters

Parameter Type — Numerical

This parameter provides a multiplier for the displayed speed value shown on the

Factory Default — 0.00 (OFF)

Changeable During Run — Yes

front panel display of the ASD.

 

 

This parameter may be used to display the rate that a commodity is being

Minimum — 0.00

 

 

 

processed by the driven load in process units (i.e., units/time).

Maximum — 200.00

 

Example: An output frequency of 100 Hz would be displayed as 50 Hz if using a multiplier of 0.5 for this parameter.

Note: PID frequency-limiting parameters are not affected by this setting (i.e., F364, F365, F367, and F368).

Display Unit Selection

Program Utilities Display Parameters

This parameter is used in conjunction with F702 to set the method in which the frequency is displayed on the front panel.

The multiplier setting of F702 will be applied to the display of all frequencies if All Frequencies are selected at this parameter.

The multiplier setting of F702 will be applied to parameters F364, F365, F367, and F368 ONLY if PID Process Data is selected at this parameter.

Settings:

0 — All Frequencies

1 — PID Process Data

Direct Access Number — F703

Parameter Type — Selection List

Factory Default — All Frequencies

Changeable During Run — Yes

Display Gradient Characteristic

Program Utilities Display Parameters

The ASD-displayed response to output speed changes will be displayed as directly proportional or inversely proportional as a function of this parameter setting.

Selecting Negative Gradient displays an increased output speed as going more negative.

Selecting Positive Gradient displays an increased output speed as going more positive.

Settings:

0 — Minus (Negative Gradient)

1 — Plus (Positive Gradient)

Direct Access Number — F705

Parameter Type — Selection List

Factory Default — Plus

Changeable During Run — Yes

H9 ASD Installation and Operation Manual

199

Page 207
Image 207