Toshiba H9 F214 F215, RR Input Point 1 Rate, RR Input Point 2 Rate, RR Input Torque Control Setup

Models: H9

1 289
Download 289 pages 12.38 Kb
Page 120
Image 120

F214

 

F215

RR Input Point 1 Rate

Direct Access Number —

F214

Program Torque Setpoints

Parameter Type — Numerical

This parameter is used to set the gain and bias of the RR input terminal when

Factory Default — 0.00

 

Changeable During Run — Yes

the RR terminal is used as the control input while operating in the Torque

 

 

Control mode.

Minimum — 0.00

 

 

Maximum — 250.00

 

RR Input Torque Control Setup

Units — %

 

Perform the following setup to allow the system to receive Torque Control

Torque Settings

input at the RR input terminal:

• Program Fundamental Standard Mode Selection Frequency Mode

 

 

RR.

 

 

• Program Fundamental Standard Mode Selection Command Mode

 

 

Selection Terminal Block.

 

 

Torque Control

 

 

Perform the following setup to allow the system to perform Torque Control

 

 

from the RR input terminal:

 

 

• Set RR Input Point 1 Rate (F214).

 

 

• Set RR Input Point 1 Setting (F210) — the input analog signal level that

 

 

corresponds to the torque setting at RR Input Point 1 Rate.

 

 

• Set RR Input Point 2 Rate (F215).

 

 

• Set RR Input Point 2 Setting (F212) — the input analog signal level that

 

 

corresponds to the frequency setting at RR Input Point 2 Rate.

 

 

• Provide a Run command (F and/or R).

 

 

Torque Control is accomplished by establishing an associated V/f output pattern

 

 

for a given RR input level.

 

 

Once set, as the RR input voltage changes, the output torque of the ASD will

 

 

vary in accordance with the above settings.

 

 

This parameter sets RR Input Point 1 Rate and is the output torque value that

 

 

is associated with the setting of RR Input Point 1 Setting when operating in

 

 

the Torque Control mode.

 

 

This value is entered as 0% to 250% of the rated torque.

 

 

RR Input Point 2 Rate

Direct Access Number —

F215

Program Torque Setpoints

Parameter Type — Numerical

This parameter is used to set the gain and bias of the RR input terminal when

Factory Default — 100.00

 

Changeable During Run — Yes

the RR terminal is used as the control input while operating in the Torque

 

 

Control mode.

Minimum — 0.00

 

Torque Control is accomplished by establishing an associated V/f output

Maximum — 250.00

 

pattern for a given RR input level.

Units — %

 

 

 

This parameter sets RR Input Point 2 Rate and is the output torque value that is associated with the setting of RR Input Point 2 Setting when operating in the Torque Control mode.

This value is entered as 0% to 250% of the rated torque.

See RR Input Point 1 Rate for more information on this setting.

112

H9 ASD Installation and Operation Manual