F214 |
| F215 | |
RR Input Point 1 Rate | Direct Access Number — | F214 | |
Program ⇒ Torque ⇒ Setpoints | Parameter Type — Numerical | ||
This parameter is used to set the gain and bias of the RR input terminal when | Factory Default — 0.00 |
| |
Changeable During Run — Yes | |||
the RR terminal is used as the control input while operating in the Torque | |||
|
| ||
Control mode. | Minimum — 0.00 |
| |
| Maximum — 250.00 |
| |
RR Input Torque Control Setup | Units — % |
| |
Perform the following setup to allow the system to receive Torque Control | Torque Settings | ||
input at the RR input terminal: | |||
• Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode |
|
| |
⇒ RR. |
|
| |
• Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode |
|
| |
Selection ⇒ Terminal Block. |
|
| |
Torque Control |
|
| |
Perform the following setup to allow the system to perform Torque Control |
|
| |
from the RR input terminal: |
|
| |
• Set RR Input Point 1 Rate (F214). |
|
| |
• Set RR Input Point 1 Setting (F210) — the input analog signal level that |
|
| |
corresponds to the torque setting at RR Input Point 1 Rate. |
|
| |
• Set RR Input Point 2 Rate (F215). |
|
| |
• Set RR Input Point 2 Setting (F212) — the input analog signal level that |
|
| |
corresponds to the frequency setting at RR Input Point 2 Rate. |
|
| |
• Provide a Run command (F and/or R). |
|
| |
Torque Control is accomplished by establishing an associated V/f output pattern |
|
| |
for a given RR input level. |
|
| |
Once set, as the RR input voltage changes, the output torque of the ASD will |
|
| |
vary in accordance with the above settings. |
|
| |
This parameter sets RR Input Point 1 Rate and is the output torque value that |
|
| |
is associated with the setting of RR Input Point 1 Setting when operating in |
|
| |
the Torque Control mode. |
|
| |
This value is entered as 0% to 250% of the rated torque. |
|
| |
RR Input Point 2 Rate | Direct Access Number — | F215 | |
Program ⇒ Torque ⇒ Setpoints | Parameter Type — Numerical | ||
This parameter is used to set the gain and bias of the RR input terminal when | Factory Default — 100.00 |
| |
Changeable During Run — Yes | |||
the RR terminal is used as the control input while operating in the Torque | |||
|
| ||
Control mode. | Minimum — 0.00 |
| |
Torque Control is accomplished by establishing an associated V/f output | Maximum — 250.00 |
| |
pattern for a given RR input level. | Units — % |
| |
|
|
This parameter sets RR Input Point 2 Rate and is the output torque value that is associated with the setting of RR Input Point 2 Setting when operating in the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
See RR Input Point 1 Rate for more information on this setting.
112 | H9 ASD Installation and Operation Manual |