LED Display

LCD Display

 

Possible Causes

 

 

 

 

 

 

 

 

E-24

Optional Expansion

Optional Expansion Input Terminal Board 2 is defective.

 

Input Terminal Board

 

 

 

2 Error

 

 

 

 

 

 

E-25

Stop Positioning

Load movement while stopped.

 

F381 setting is too low.

 

Retention Error

 

 

 

 

 

Encoder malfunction.

 

 

• Creep speed is too high.

 

 

 

 

E-26

CPU2 Fault

CPU malfunction.

 

Control board malfunction.

 

 

 

 

 

 

E-50/E-51

Sink/Source Setting

Improperly positioned Sink/Source jumper on the Terminal board or on an

 

 

option device (see J100 at the Terminal PCB of the ASD).

 

Error

 

 

Sink/Source configuration is incorrect.

 

 

 

 

 

 

EEP1

EEPROM Fault

EEPROM write malfunction.

 

• Make a service call.

 

 

 

 

 

 

EEP2/EEP3

EEPROM Data Fault

EEPROM read malfunction.

 

• Make a service call.

 

 

 

 

 

 

EF1/EF2

 

Ground fault at the motor.

 

(Earth) Ground Fault

Ground fault at the output of the ASD.

 

 

• Current leakage to Earth Ground.

 

 

 

 

EPHI

Input Phase Failure

3-phase input to the ASD is low or missing at the R, S, or T input terminals.

 

 

 

 

EPHO

Output Phase Failure

3-phase output from the ASD is low or missing at the U, V, or W output

 

 

 

terminals or at the input to the motor.

 

 

 

 

ERR2

RAM Fault

Internal RAM malfunction.

 

• Make a service call.

 

 

 

 

 

 

ERR3

ROM Fault

Internal ROM malfunction.

 

• Make a service call.

 

 

 

 

 

 

ERR4

 

CPU malfunction.

 

CPU Fault

Control board malfunction.

 

 

• Make a service call.

 

 

 

 

ERR5

 

Communication time out error.

 

Communication

Communication malfunction.

 

Error

 

 

 

 

 

• Improper or loose connection.

 

 

Improper system settings.

 

 

 

 

ERR6

Gate Array Fault

Main Gate Array is defective.

 

 

 

 

ERR7

Low Current

Improper Low Current detection level settings at F609 F612.

 

 

 

 

ERR8

Option Device Fault

Check installation, connections, and option device manual.

 

 

 

 

ERR9

Flash Memory Fault

Flash memory malfunction.

 

• Make a service call.

 

 

 

 

 

 